MANUAL PRIOAIR[006]

Electrical connection |
9
8.3 Installation variations
The installation is possible in any mounting position.
Installation with
mounting bracket
Note:
The mounting
bracket is
available in our
accessory range.
Mount the mounting
bracket on the fan,
see adjacent image.
9 Electrical connection
9.1 Safety information
Warning: Danger from electrical voltage!
Observe the 5 rules of electrical safety, see 2.3 5 rules of electrical safety, page 2.
Prevent the ingress of water into the connection box.
Electrical connection may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page
1.
Observe and respect local conditions, regulations and laws.
Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
Warning: Danger due to electrostatic influence on medical implants (e.g. cardiac pacemaker)!
Persons with medical implants (e.g. cardiac pacemaker) should keep enough distance to the fan.
9.2 Preconditions
Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.
Safety elements may not be dismantled, circumvented or deactivated.
Install a circuit breaker in the permanent electrical installation, with a contact opening of at least 3 mm at each pole.
9.3 Connection
Check if the data on the nameplate matches the
connection data.
Complete the electrical connection according to the
circuit diagram.
Lay the connection cables in the terminal box in such
a way that allows the cover of the terminal box to be
closed without resistance.
Use all of the locking screws.
Insert the screws by hand to avoid damaging the
thread.
Tighten all glands well in order to guarantee
protection class IP.
Screw the lid of the terminal box/inspection switch
evenly tight.
Connect the cable end in a dry environment.
| 006