TOPVEX SF OPERATING MAINTENANCE 130323A002
Table Of Contents
Commissioning
|
13
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
→ Alarm settings → Alarm limits
Set the alarm limits and allowed
deviations for the different
functions
→ Alarm delays
Set the alarm delays and allowed
deviation delays for the different
functions
→ Restore alarm
Reset the service alarm (filter
alarm).
Restore factory
settings: No
Restore user
settings: No
In this menu, it is possible to restore
all parameters to their factory
settings or to the user settings they
were saved as earlier.
Select Yes or No
Save user
settings
No
The current configuration can be
saved in a separate memory area
and can later be restored using the
previous menu, Restore user
settings. Select Yes or No
Darker gray area, log in to
“Administrator level”
code 3333
→ Configuration
→
Inputs/Outputs
Setup for inputs and outputs.
→
Sensor settings
Setup of sensor types and control
range.
→
Control function
Control function
Mode:
Supply air control
Set type of temperature control
function you want the unit to
operate under. Choose between
Supply air control, Outdoor
comp. supply
More information in chapter 4.4
Fan control Frequency manual
*Set type of fan control function
you want the unit to operate under.
Choose between Pressure
control (option accessory),
Frequency manual.
→
Extra sequency Y4
Mode extra sequence
Y4
Active w cool recov
Can be configured to one of the
following alternatives:
Active, Active with cooling
recovery, Active with
enthalpy control and Active
with both cooling recovery
and enthalpy control.
→
Extra sequency Y5
Extra sequence Y5 can be
configured to Active or Not
active.
→
Heating
Type of heater
→
Cooling
Type of cooler
→
Pump control
P1–Heating
P1–Cooling
Set parameters for pump control.
If, for any of the control circuits, no
output is configured for pump
control these settings will be
ignored.
130323 | A002