TOPVEX SF OPERATING MAINTENANCE 130323A002
Table Of Contents
12
|
Commissioning
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
Extra sequence Y5
Auto
Manual set: 0.0
Set the Extra sequence to Auto,
Manual or Off
Not used in default setting.
Motor control1
Auto
Motor control2
Auto
Motor control
Note:
See Corrigo manual-
Ventilation application for
more information.
→ Settings
In this menu group the settings for
the activated functions are
available. Depending on which
choices have been made in the
configuration menu some of the
possible alternatives may not be
displayed.
→ Control temp
Supply air control
P-band: 33.0°C
I-time: 100.0 sec
Set P-band and I-time for the
Supply air control function
Note:
See Corrigo manual-
Ventilation application for
more information.
Shutdown mode
P-band: 100.0°C
I-time: 100.0 sec
Set P-band and I-time for the
Shutdown function
Note:
See Corrigo manual-
Ventilation application for
more information.
→ Frost protection
Active
Setp shutdown:
25.0°C
P-band active: 5.0°
C
Status for frost protection.
When running mode switched to
"Off".
Shutdown controller will control the
heating output to maintain a
constant settable temperature at
the frost protection sensor for the
hot water coil.
If frost protection temperature falls
below Frost protection Alarm
level + settable P-Band for frost
protection, it will rise the internal
signal and force the heating valve
to open to avoid freeze-up of hot
water coil.
Fast stop at frost
protection alarm
Yes
Set the fast stop of the unit in case
of frost protection alarm to Yes or
No.
Sequency with frost
protection
Y1–Heating
Frost protection control.
Is available for Y1 heating, Y4
extra sequenceor on both Y1
and Y4.
→ Control
pressure
Pressure control
SAF
P-band: 500.0 m³/h
I-time: 60.0 sec
Min. output: 0%
Set P-band, I-time and Min. output
for the supply air.
Only shown if VAV accessory is
used.