TOPVEX SF OPERATING MAINTENANCE 130323A002

Commissioning
|
11
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
Manual/Auto
In this menu the running mode of all
the configured output signals and a
number of control functions can be
manually controlled.
The supply air controller's output
signal can be manually set
(Manual/Auto) to any value
between 0 and 100%. The
temperature output signals will
change accordingly if they are in
Auto mode. It is also possible to
manually control each of the
temperature output signals
individually.
Since leaving any of the outputs in
manual control will disrupt the
normal control, an alarm will be
generated as soon as any output is
set to a manual mode.
Supply temp.
contr.
Auto
Manual set: 0.0
Set the supply air temperature
controller to Auto, Manual or Off.
Set the output signal between 0-
100%.
The outputs Y1, Y2 and Y3, if in
Auto-mode, will follow the signal
according to the set split values.
SAF: Auto
Manual set: 0.0
Set the output signal for SAF
(supply air fan) to:Auto,
Manual,1/2–speed or 1/1–
speed.
Heating
Auto
Manual set: 100.0
Set the heating to Auto, Manual or
Off.
Set the manual output 0-100%.
Cooling
Auto
Manual set: 0.0
Set the cooling to Auto, Manual or
Off
Set the manual output 0-100%
Note:
Needs to be activated in
order to be visible here
P1–Heating
Auto
Set the pump control for the
heating coil to Auto, On or Off
P1–Cooling
Auto
Set the pump control for the cooling
coil to Auto, On or Off
Fire damper
Auto
Set the Fire damper to Auto, Open
or Close
Note:
Needs to be activated in
order to be visible here
Configuration of fire damper
functions are made at
Administrator level
Outdoor air
damper
Auto
Set the Outdoor air damper to
Auto, Open or Close
Exhaust air
damper
Auto
Set the Exhaust air damper to Auto,
Open or Close
130323 | A002