COMMISSIONING RECORD206951 (A008) FORM
Table Of Contents
Commissioning record |
9
Alarm settings Def. settings Set value Alarm settings Def.settings Set value
31. Supply air fan control error 86. Time for service
Class: B _____ Class: C _____
Delay: 60 S _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: Rotation guard
exchanger
_____ Alarm text: Output in manual
mode
Max. diff. between setpoint and actual
pressure:
VAV units — 50 Pa _____
CAV size 03, 04 — 80
m
3
/h
_____
CAV size 06, 08, 09 —
160 m
3
/h
_____
CAV size 11, 12, 15 —
250 m
3
/h
_____
32. Extract air fan pressure control error 87. Manual extra sequence Y4
Class: B _____ Class: C _____
Delay: 4 min _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: Extract air fan control
error
_____ Alarm text: Manual Y4–extra
sequence control
Max. diff. between setpoint and actual
pressure:
VAV units — 50 Pa _____
CAV size 03, 04 — 80
m
3
/h
_____
CAV size 06, 08, 09 —
160 m
3
/h
_____
CAV size 11, 12, 15 —
250 m
3
/h
_____
35. Ventilation stopped 88. Restart blocked after power on
Class: C _____ Class: B _____
Delay: 0 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: Yes _____
Alarm text: Ventilation manual mode Alarm text: Restart blocked
after power on
206951 | A008