COMMISSIONING RECORD206951 (A008) FORM

6
| Commissioning record
1.3 Alarm configuration
Alarm settings Def. settings Set value Alarm settings Def.settings Set value
1. Supply air fan is out of operation 36. Manual supply air control
Class: A _____ Class: C _____
Delay: 300 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: Yes _____ Stop ventilation if alarm active: No _____
Alarm text: Run error supply air fan Alarm text: Manual support
control
2. Extract air fan is out of operation 37. Manual supply air fan mode
Class: A _____ Class: A _____
Delay: 300 s _____ Delay: 300 s _____
Stop ventilation unit if alarm active: Yes _____ Stop ventilation unit if alarm active: Yes _____
Alarm text: Run error extract air fan Alarm text: Run error supply air
fan
3. P1–heater is out of operation
Class: B _____ Class: B _____
Delay: 5 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: Run error P1–heater
Alarm text: Manual supply air
fan freq. control
4. P1–cooler is out of operation 39. Manual extract air fan mode
Class: B _____ Class: C _____
Delay: 5 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: No _____ Stop ventilation unit if alarm active: No _____
Alarm text: Run error P1–cooler
Alarm text: Manual extract air
fan mode
6. Filter guard 40. Manual extract air fan freq. control
Class: B _____ Class: C _____
Delay: 300 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: Yes _____ Stop ventilation unit if alarm active: No _____
Alarm text: Filter guard
Alarm text: Manual extract air
fan freq. control
10. Fire alarm 41. Manual heater control
Class: A _____ Class: C _____
Delay: 0 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: Yes _____ Stop ventilation unit if alarm active: No _____
Alarm text: Fire alarm
Alarm text: Manual heater
control
11. External switch 42. Manual exchanger control
Class: C _____ Class: C _____
Delay: 0 s _____ Delay: 0 s _____
Stop ventilation unit if alarm active: Yes _____ Stop ventilation unit if alarm active: No _____
Alarm text: External switch Alarm text: Manual exchanger
control
206951 | A008