Compact Air Handling Units Topvex FR, SR, TR, SC, SX/C, TX/C, FC, SF Commissioning Record Document in original language | 206951 · A008 GB
© Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 Commissioning record ......................................1 1.1 Function settings....................................1 1.2 Setting the weekly program......................5 1.3 Alarm configuration ................................6 1.4 Notes and signatures ............................
Clear form 1 1 Commissioning record | Commissioning record Company: Responsible: Customer: Date: Installation: Object/Unit: Item no.: Installation address: Model/Size: Serial no.: Time and date set: ˜ External connections (sensors, dampers, external alarm etc.) performed: ˜ 1.1 Weekly program set: ˜ Function settings EAF is not optional for supply air units. 1 Function Default setting Temp. (°C) Control function temp.
2 | Commissioning record Function Default settings Set value Pre-heater Off On Extra control unit Run if defrosting ™ Run if defrosting ˜ Temperature 0 °C _____ °C Pre-heater ™ ˜ Off ˜ Run if unit is running ˜ Airflow Fan control Airflow (m3/h) 1 ˜ (CAV) Airflow (m3/h) Pressure (Pa) 1 ˜ (VAV) Pressure (Pa) ˜ (VAV) Manual air control ˜ % control Manual air control ˜ % control ˜ (CAV) Manual air control Supply airflow at reduced speed _____ (%) Extract airflow at reduced speed
Commissioning record | Function Default settings Set value Frost protection (Only visible for units without EL heater) Mode (EL unit Off) On Frost limit temperature: See alarm settings/low frost guard temp See alarm settings/low frost guard temp On Set point when stopped (return water): 7° C _____ ° C P-band when running 5 _____ ™ ˜ Off ˜ Free cooling Mode: Off Activation at outdoor temp. higher than: 22° C _____ ° C Stopped at outdoor night temp.
4 | Commissioning record Function Default settings Set value External set point knob External set point knob: Off On Min. set point of knob 12 ° C _____ ° C Max. set point of knob 30 ° C _____ ° C ™ ˜ Off ˜ ˜ Off ˜ HW heat pump Pump stop mode (EL unit off): Off On Stop delay: 5 min _____ min Pump stop at outdoor temp.
Commissioning record | 1.2 Setting the weekly program Factory setting of the normal and reduced fan speed are: • Normal fan speed 07:00 to 16:00 Monday to Sunday and reduced fan speed remaining time Monday to Sunday. • Settings of 00:00 to 00:00 stops the unit. E.g. changing reduced fan speed setting from 00:00–24:00 to 00:00–00:00 will stop the unit outside the time of normal fan speed. Note: Normal fan speed has priority over a reduced fan speed.
6 | Commissioning record 1.3 Alarm configuration Alarm settings Def. settings Set value 1. Supply air fan is out of operation Alarm settings Def.settings Set value 36. Manual supply air control Class: A _____ Class: C _____ Delay: 300 s _____ Delay: 0s _____ Stop ventilation unit if alarm active: Yes _____ Stop ventilation if alarm active: No _____ Alarm text: Run error supply air fan Alarm text: Manual support control 2. Extract air fan is out of operation 37.
Commissioning record | Alarm settings Def. settings Set value Class: B _____ Delay: 0s _____ Stop ventilation unit if alarm active: No _____ Alarm text: External alarm 12. External alarm Alarm settings Def.settings Set value Class: C _____ Delay: 0s _____ Stop ventilation unit if alarm active: No _____ Alarm text: Manual cooler control 43. Manual cooler control 15. High supply air temp 44.
8 | Commissioning record Alarm settings Def. settings Set value Def.settings Set value Class: B _____ Class: B _____ Delay: 30 min Stop ventilation unit if alarm active: No _____ Delay: 5s _____ _____ Stop ventilation unit if alarm active: No _____ Alarm text: Low extract temp.: Alarm text: Sensor error exhaust air temp.: High extract temp.: 10° C 22. Low extract air temp. Alarm settings 53. Sensor error exhaust air temp. _____ 23.
Commissioning record | Alarm settings Def. settings Set value Def.settings Set value Class: B _____ Class: C _____ Delay: 60 S Stop ventilation unit if alarm active: No _____ Delay: 0s _____ _____ Stop ventilation unit if alarm active: No _____ Alarm text: Rotation guard exchanger _____ Alarm text: Output in manual mode Max. diff.
10 | Commissioning record 1.4 Notes and signatures Signature: ________________________________________________________________________________________ Location: __________________________________________________________________________________________ Date: _____________________________________________________________________________________________ Phone no.
206951 | A008