EDM SYSHP MINI DCI
84
7.10.3 ADDITIONAL HEATING SOURCE MENU
MENU > FOR SERVICEMAN > OTHER HEATING SOURCE > ADDITIONAL
HEATING SOURCE
To enter the ADDITIONAL HEATING SOURCE menu, navigate to the OTHER
HEATING SOURCE menu, scroll to YES on the ADDITIONAL HEATING SOURCE
line and press OK.
Figure 3-7.32: ADDITIONAL HEATING SORUCE menu
T4_AHS_ON sets the ambient temperature below which the addional heang source is used. If the ambient temperature is
above T4_ASH_ON, the addional heang source is not used. The relaonship between operaon of the addional heang
source and the ambient is shown in the picture below.
dT1_ASH_ON sets the temperature dierence between the heat pump’s leaving water set temperature (T1S) and the heat
pump’s leaving water temperature (T1) above which the addional heang source is on. When T1S - T1 ≥ dT1_AHS_ON the
addional heang source is on.
dT1_ASH_OFF sets the temperature dierence between the heat pump’s leaving water set temperature (T1S) and the heat
pump’s leaving water temperature (T1) below which the addional heang source is o. When T1 - T1S ≥ dT1_AHS_OFF the
addional heang source is o. Note: dT1_ASH_OFF can take values in the range -5°C to 0°C.
t_ASH_DELAY sets the delay between the compressor starng and the addional heang source being turned on.
Abreviaons:
AHS: Addional heang source
T1: Heat pump leaving water temperature
T1S: Heat pump leaving water set temperature
T4: Outdoor ambient temperature
Compressor
Time
Heat mode by
AHS only
Heat mode by heat
pump and AHS
Heat mode by
heat pump
Figure 3-7.33: T4_AHS_ON
Abreviaons:
AHS: Addional heang source
T4: Outdoor ambient temperature
Figure 3-7.34: Addional heang source delay