EDM SYSHP MINI DCI

7
Calculate condioned surface area
Select the heat emiers (type, quanty, water temperature and heat load)
Decide whether to include AHS and set AHSs switching temperature
Decide whether backup electric heater is enabled or disabled
Determine required total heat load on outdoor units
Set capacity safety factor
Select power supply
Yes No
Select a larger model or enable
backup electric heater operaon
4 System and Design Unit Selecon
4.1 Selecon Procedure
Step 1: Total heat load calculaon
Step 2: System conguraon
Step 3: Selecon of outdoor units
Notes:
1. If the required water temperatures of the heat emiers are not all the same, the Mini Heat Pump’s outlet water temperature seng should be set at the
highest of the heat emier required water temperatures. If the water outlet design temperature falls between two temperatures listed in the outdoor
units capacity table, calculate the corrected capacity by interpolaon.
2. If the outdoor unit selecon is to be based on total heang load and total cooling load, select Mono units which sasfy not only the total heang load
requirements but also the total cooling load requirements.
Provisionally select Mini Heat Pump unit capacity based on nominal capacity
Correct capacity of the outdoor units for the following items:
Outdoor air temperature / Outdoor humidity / Water outlet temperature
1
/
Altude / An-freeze uid
Is corrected Mini Heat Pump unit capacity Required total heat load on
outdoor units
2
Mini Heat Pump system
selecon is complete