EDM SYSHP MINI DCI
78
Abbreviaons:
T5: DHW tank water temperature
T5S: DHW set temperature
T5stop: DHW mode leaving water temperature operang limit
t_DHWHP_MAX sets the maximum length of me that the heat pump will run in DWH
mode before switching to space heang mode or space cooling mode if a requirement
for space heang/cooling modes exists. When running in DHW mode, the heat pump
becomes available for space heang/cooling either as soon as the DHW tank water
temperature (T5) reaches the DHW set temperature (T5S) or aer t_DHWHP_MAX
minutes have elapsed.
t_DHWHP_RESTRICT sets the maximum length of me that the heat pump will run in
space heang or space cooling modes before switching to DHW mode, if a requirement
for DHW mode exists. When running in space heang mode or space cooling mode,
the heat pump becomes available for DHW mode either as soon as the space heang/
To enter the DHW PRIORITY menu, navigate to the DHW MODE SETTING menu, scroll to YES on the DHW PRIORITY line and
press OK.
cooling set temperatures have been reached (refer to Part 3, 7.5 “COOL MODE SETTING Menu” and Part 3, 7.6 “HEAT MODE
SETTING Menu”) or aer t_DHWHP_MAX minutes have elapsed.
Figure 3-7.13 illustrates the eects of t_DHWHP_MAX and t_DHWHP_RESTRICT when DHW PRIORITY is enabled. The heat
pump inially runs in DWH mode. Aer t_DHWHP_MAX minutes, T5 has not reached the minimum of T5S and Tstop and the
heat pump run in space heang or space cooling modes. Aer t_DHWHP_restrict minutes have elapsed, the heat pump switch
to DHW mode.
7.4.6 DHW PUMP MENU
MENU > FOR SERVICEMAN > DHW MODE SETTING > DHW PUMP
To enter the DHW PUMP menu, navigate to the DHW MODE SETTING menu, scroll to
YES on the DHW PUMP line and press OK.
A DHW pump can be used to circulate the water in the DHW piping system.
TIMER RUNNING sets whether or not the user is able to set pump start mes on the
DHW PUMP tab of the DOMESTIC HOT WATER (DHW) menu. For installaons with a
Figure 3-7.14: DHW PUMP menu
DHW pump, select ON so that the user is able to set pump start mes. For installaons without a DHW pump, select OFF to
hide the start me opons on the DHW PUMP tab of the DOMESTIC HOT WATER (DHW) menu.
Figure 3-7.12: DHW PRIORITY menu
Figure 3-7.13: Operaon in DHW PRIORITY
Time
Restart
Heang
water
Space heating/
cooling
operation
Heang
water