9 Error Code Table
Table 3-9.1: Error code table
Table connued on next page …
Error code Content
C7 Transducer module temperature too high protect
E0
E8
Water ow failure
E1 Phase sequence error
E2 Communicaon error between outdoor unit and user interface
E3 Backup electric heater exchanger water outlet temperature sensor error
E4 Domesc hot water tank temperature sensor error
E5 Air side heat exchanger refrigerant outlet temperature sensor error
E6 Outdoor ambient temperature sensor error
E9 Sucon pipe temperature sensor error
EA Discharge pipe temperature sensor error
Ed Water side heat exchanger water inlet temperature sensor error
EE Hydronic system EEPROM error
F1 DC generatrix voltage is too low
H0
Communicaon error between refrigerant system main control chip and hydronic system
main control chip
H1 Communicaon error between refrigerant system main control chip and inverter driver chip
H2 Water side heat exchanger refrigerant inlet (liquid pipe) temperature sensor error
H3 Water side heat exchanger refrigerant outlet (gas pipe) temperature sensor error
H5 Room temperature sensor error
H6
HH
DC fan error
H7 Abnormal main circuit voltage
H8 Pressure sensor error
H9 Auxiliary heat source water outlet temperature sensor error
HA Water side heat exchanger water outlet temperature sensor error
HF Refrigerant system EEPROM error
P0
HP
Low pressure protecon
P1 High pressure protecon
P3 Compressor current protecon
P4 Discharge temperature protecon
P5
High temperature dierence between water side heat exchanger water inlet and water outlet
temperatures protecon
P6
H4
Inverter module protecon
L0 Inverter module protecon
L1 DC bus low voltage protecon
L2 DC bus high voltage protecon
L4 MCE error
L5 Zero speed protecon
L7 Phase sequence error