Keep dry
Do not fasten the black plastic
cover on the vent valve at the
topside of the unit when the
system is running. Open air
purge valve, turn anticlockWise
at least 2 full turns to releaseair
from the system.
That in case of an installaon with a domesc hot water tank, only the use of propylene glycol is allowed. In other
installaons the use of ethylene glycol is ne.
That no automove glycol is used because their corrosion inhibitors have a limited lifeme and contain silicates that can
foul or plug the system;
That galvanized piping is not used in glycol systems since it may lead to the precipitaon of certain elements in the glycol’s
corrosion inhibitor;
To ensure that the glycol is compable with the materials used in the system.
3.5 Water Flow Switch
Water may enter into the ow switch and cannot be drained out and may
freeze when the temperature is low enough. The ow switch should be
removed and dried, then can be reinstalled in the unit.
Counterclockwise rotaon, remove the water ow switch.
Drying the water ow switch completely.
3.6 Adding Water
Connect the water supply to the ll valve and open the valve.
Make sure the automac air purge valve is open (at least 2 turns).
Refer to Figure 3-3.3.
Fill with water unl the manometer indicates a pressure of approximately
2.0 bars. Remove air in the circuit as much as possible using the air purge
valve. Air in the water circuit could lead to malfuncon of the backup
electric heater.
Figure 3-3.2: Water ow switch
Figure 3-3.3: Air purge valve
3.7 Water Piping Insulaon
The complete water circuit including all piping, water piping must be insulated to prevent condensaon during cooling
operaon and reducon of the heang and cooling capacity as well as prevenon of freezing of the outside water piping
during winter. The insulaon material should at least of B1 re resistance rang and complies with all applicable legislaon.
The thickness of the sealing materials must be at least 13mm with thermal conducvity 0.039W/mK in order to prevent
freezing on the outside water piping. If the outdoor ambient temperature is higher than 30°C and the humidity is higher than
RH 80%, the thickness of the sealing materials should be at least 20mm in order to avoid condensaon on the surface of the
seal.