EDM SYSHP MINI DCI
12.2 PREHEATING FOR FLOOR
Preheat for floor is
running for 25 minutes.
Water flow temperature is 20°C.
89
7.15.3 PREHEATING FOR FLOOR
MENU > FOR SERVICEMAN > SPECIAL FUNCTION > PREHEATING FOR FLOOR
During inial start-up and when water temperature is low, it is important that the
water is heated gradually. Or it may result in concrete oors cracking due to rapid
temperature change.
T1S sets the heat pump’s leaving water set temperature in preheang for oor mode.
Figure 3-7.48: Preheang for oor menu
dT1SH sets the temperature dierence between the heat pump’s leaving water set temperature (T1S) and the heat pump’s
leaving water temperature (T1) above which the heat pump provides heated water to the oor heang loops. When T1S – T1
≥ dT1SH the heat pump provides heated water to the oor heang loops.
t_fristFH sets the duraon of preheang for oor mode.
The operaon of the unit during preheang for oor mode is illustrated in Figure 3-7.49.
Abreviaons:
t_interval_H: Compressor re-start delay in space heang mode. (Refer to Part 3, 7.6 “HEAT
MODE SETTING Menu”).
Whilst the preheang for oor operaon is running, the number of minutes that it has been running for and the heat pump’s
leaving water temperature are displayed on the user interface. During the preheang for oor operaon all buons except OK
are inacvated. To exit the preheang for oor operaon, press OK and then select YES when prompted. Refer to Figure 3-7.50.
Figure 3-7.49: Preheang for oor
Compressor
Time
Punp
Figure 3-7.50: Preheang for oor screens
Before oor heang, if large a amount of water remains on the oor, the oor may be warped or even rupture during oor
heang operaon, in order to protect the oor, oor drying is necessary, during which the temperature of the oor should be
increased gradually.