EDM SYSHP MINI DCI
8
4.2 Mini Heat Pump Leaving Water Temperature (LWT) Selecon
The recommended design LTW ranges for dierent types of heat emier are:
For oor heang: 30 to 35°C
For fan coil units: 30 to 45°C
For low temperature radiators: 40 to 50°C
4.3 Opmizing System Design
To get the most comfort with the lowest energy consumpon with Mini Heat Pump, it is important to take account of the
following consideraons:
Choose heat emiers that allow the heat pump system to operate at as low a hot water temperature as possible whilst
sll providing sucient heang.
Make sure the correct weather dependency curve is selected to match the installaon environment (building structure,
climate) as well as ender user’s demands.
Connecng room thermostats (eld supplied) to the hydronic system helps prevent excessive space heang by stopping
the outdoor unit and circulator pump when the room temperature is above the thermostat set point.