5
1.2 System Conguraons
Mini Heat Pump Monobloc can be congured to run with the electric heater either enabled or disabled and can also be used
in conjuncon with an auxiliary heat source such as a boiler.
The chosen conguraon aects the size of heat pump that is required. Three typical conguraons are described below.
Refer to Figure 1-1.2.
Conguraon 1: Heat pump only
The heat pump covers the required capacity and no extra heang capacity is necessary.
Requires selecon of larger capacity heat pump and implies higher inial investment.
Ideal for new construcon in projects where energy eciency is paramount.
Conguraon 2: Heat pump and backup electric heater
Heat pump covers the required capacity unl the ambient temperature drops below the point at which the heat pump
is able to provide sucient capacity. When the ambient temperature is below this equilibrium point (as shown in Figure
1-1.2), the backup electric heater supplies the required addional heang capacity.
Best balance between inial investment and running costs, results in lowest lifecycle cost.
Ideal for new construcon.
Conguraon 3: Heat pump with auxiliary heat source
Heat pump covers the required capacity unl the ambient temperature drops below the point at which the heat pump
is able to provide sucient capacity. When the ambient temperature is below this equilibrium point (as shown in Figure
1-1.2), depending on the system sengs, either the auxiliary heat source supplies the required addional heang capacity
or the heat pump does not run and the auxiliary heat source covers the required capacity.
Enables selecon of lower capacity heat pump.
Ideal for refurbishments and upgrades.
Figure 1-1.2: System conguraons
Conguraon 1
Conguraon 2
Conguraon 3
Heat pump capacity
Required capacity
Ambient temperature
Highest temperature
(No more heang)
Lowest tern perature
(Design temperature)
Equilibrium points
Minimum required capacity (OkW)
Maximum required capacity