IMO SET
Table Of Contents
14
THE PIPE RUN
When installing the pipe run in your home during the building period, this should be done while the walls are still
open and all possible obstacles (water pipes, electrical runs etc.) are visible.
Note! Remember that branch pipes to inlet valve should never point downwards (fig. 8.2).
Where pipe runs are not visible (inside walls and floors) you will sometimes have to go through joists in the floor.
This must be done according to fig. 8.3 - 8.5 and 8.8.
Note! The low voltage wire must follow an uninterrupted route from inlet to inlet and all the way to the power unit.
Strap or tape the wire to pipe (fig. 8.6 and 8.7).
Pipe runs in existing homes should be installed in closets/cupboards, subordinate rooms, loft space or built-in in
corners. (If necessary, use pipe straps as shown in fig. 8.6).
When going through existing walls/floors, drill an inspection hole to verify that the wall/floor does not contain any
electrical conductors or water pipes. Use a piece of steel wire and a flash light to look for obstacles. See fig. 8.10
Fig. 8.1. The pipe runs should be installed when framework Fig. 8.2. First install the inlet valve farthest off from
is up, but before your walls are plated. Start on the top the power unit. Press pipe into the sharp 90
o
elbow.
floor and drill a small hole in the ground beam under the Remember that 16 mm of the pipe goes into every bend.
inlet valve. Check for obstructions. Then drill a 57 mm Measure the correct pipe length and make a square cut.
hole through the ground beam. Centre of the hole should Scrape off all burrs. Glue pipe runs. Connect pipe to
be positioned as shown in fig. 8.1 main pipe using WYE bend.
Fig. 8.3 - 8.5. Pipe run in connection with joists.
Fig. 8.6. Pipe straps. Fig. 8.7. Low voltage wire stripped or taped to pipe.
Fig. 8.8. If holes have to be made through joists, Fig. 8.9. To ease the installation Fig. 8.10. Drill an inspection hole and check
these have to be positioned in the middle of the of the low voltage wire, use a weight for obstructions in existing walls
joist, and preferably 50 - 80 cm from the closest at the end of the wire.
supporting wall.