UM AER 01 N 1GB
Table Of Contents
- CONTENTS
- 1. INTRODUCTION
- 2. INPUTS/OUTPUTS DESCRIPTION
- 3. ROOM AIR TEMPERATURE CONTROL
- 3.1. SUMMER/WINTER SWITCHING
- 3.2. UNIT ON/OFF
- 3.3. COMPRESSOR CONTROL
- 3.4. DEFROST MODE
- 3.5. MAIN FAN
- 3.6. TEMPERATURE-BASED FREECOOLING AND FREEHEATING CONTROL
- 3.7. THREE DAMPERS ECONOMIZER OPTION
- 3.8. Supply air temperature minimum limit
- 3.9. FRECO OPTION
- 3.10. THERMODYNAMIC RECOVERY OPTION - TRECO
- 3.11. AUXILIARY HEATING
- 3.12. Set point compensation
- 4. ROOM AIR QUALITY CONTROL
- 5. SMOKE DETECTOR
- 6. SCHEDULING
- 7. USER INTERFACE
- 8. ALARM MANAGEMENT
- 9. SERVICING (CAREL)
- 10. MENU DESCRIPTION (CAREL)
English
56 SysAer
Main screens
code
Item Unit Description
M0
Hour - The hour is displayed if a cloack board is present in the controller or if the unit is connected in Plan to a Master unit with a clock board fitted.
Unit (address) - Unit address on the Plan network
Indoor (room)
temperature
°C Room temperature
Unit status -
ON : the unit is running correctly.
OFF by alarm : one or several alarms don't allow the unit to start.
OFF by PLAN : if the unit is a Slave unit on Plan, it is stopped by the Master unit.
OFF by Supervisor : if a the unit is connected to a supervisor, it can stop the unit.
OFF by scheduling : if a clock board is fitted, scheduling can stop the unit.
OFF by Digital Input : unit OFF by digital input ID5 (if selected in the Service menu)
OFF by display : OFF selected via the display ON/OFF
Mode Unoccupied : if a clock board is present and the Unoccupied option is selected for scheduling, the unit is in unoccupied mode if the hour is outside
the programmed hour band.
Starting… : appears for 5 seconds at unit start-up.
M1
Hour / Date -
Air quality /
Room humidity /
Outdoor temp.
%
%rH
°C
The room air quality is displayed in priority if the option has been chosen. The room humidity is displayed in second priority if the dehumidification or the
Economizer management in enthalpy have been chosen. Finally, the outdoor temperature is displayed if the Economizer management in temperature or
the setpoint compensation have been selected.
Unit status -
M2
Hour / Date -
Active temperature
setpoint
°C
Temperature setpoint currently used by the unit to regulate the room temperature, determined from the manual setpoints, the unoccupied setpoints and
the setpoint compensation
Unit status -
M3
Unit mode
Summer /
Winter
Scheduling /
Only displayed if the clock board is present. is for function active, is for function inactive.
Dehumidification / Only displayed if the room humidity sensor is connected.
Set. compensation / Only displayed if the outdoor temperature sensor is connected.