UM AER 01 N 1GB

Table Of Contents
English
55SysAer
Main
menu Q0
Item
Screen
code
Parameter Unit Min Fact. Max Description / Note
SERVICE
PLAN units activation
PM, PN,
PO
Each unit activation N/Y N
Allows to activate and deactivate some units of the Plan network (only on the
Master unit). For example, if one unit must be diconnected, it is necessary to
deactivate it, otherwise, an alarm will be generated on the Master unit until the
missing unit is connected again.
PLAN units
configuration
PP, PQ, PR
Each unit
configuration
D/S D
Only on Master unit, when the Plan network is configured in Master/Slave. Each unit
can be configured in Display only (D) or in Slave (S). In Slave, the unit will run in the
same way as the Master unit.
Thermostat digital
inputs configuration
PS Enabling N/Y N Enables the use of a thermostat to totally run the unit (compressors…) (on demand)
PT
Summer/Winter ID2/ID12/B5 B5 Digital input configuration for Summer/Winter selection.
Electrical heaters ID2/ID12/B6 ID2 Digital input configuration to run the electrical heaters.
Smoke detector PU Activation N N Smoke detector activation
New password PV New Service pwd - 0 - 9999
MANUFACTURER
Factory reserved
ON/OFF UNIT
Unit status N0 Unit status See the Unit ON/OFF part.
Unit status N0 ON/OFF change
Switch
ON / OFF
Pressing the "Enter" key switches the unit from ON/OFF to OFF/ON
SUMMER /
WINTER
Summer/winter mode R0
Summer/winter
change
-SUMMER- /
-WINTER-
SUMMER
Pressing the "Enter" key switches the unit from Summer/Winter to Winter/Summer,
unless auto changeover or Digital input are selected. See the Summer/winter part.
UNIT SELECTION
Unit selection L0
Pressing the "Enter" key makes the display jump to the next available unit of the
PLAN network. At least two units must be connected. See the Access to the units of
the PLAN network via the single terminal part.