UM AER 01 N 1GB
Table Of Contents
- CONTENTS
- 1. INTRODUCTION
- 2. INPUTS/OUTPUTS DESCRIPTION
- 3. ROOM AIR TEMPERATURE CONTROL
- 3.1. SUMMER/WINTER SWITCHING
- 3.2. UNIT ON/OFF
- 3.3. COMPRESSOR CONTROL
- 3.4. DEFROST MODE
- 3.5. MAIN FAN
- 3.6. TEMPERATURE-BASED FREECOOLING AND FREEHEATING CONTROL
- 3.7. THREE DAMPERS ECONOMIZER OPTION
- 3.8. Supply air temperature minimum limit
- 3.9. FRECO OPTION
- 3.10. THERMODYNAMIC RECOVERY OPTION - TRECO
- 3.11. AUXILIARY HEATING
- 3.12. Set point compensation
- 4. ROOM AIR QUALITY CONTROL
- 5. SMOKE DETECTOR
- 6. SCHEDULING
- 7. USER INTERFACE
- 8. ALARM MANAGEMENT
- 9. SERVICING (CAREL)
- 10. MENU DESCRIPTION (CAREL)
English
49SysAer
Main
menu Q0
Item
Screen
code
Parameter Unit Min Fact. Max Description / Note
SERVICE
Password P0 Service password - 0 - 9999 9201
Compressors
enabling
P1
Compressor 1 N/Y Y Compressor 1 circuit 1. Allows to deactivate manually one compressor
Compressor 1B N/Y Y Compressor 2 circuit 1 (dependent on unit configuration)
P2
Compressor 2 N/Y Y Compressor 1 circuit 2 (dependent on unit configuration)
Compressor 2B N/Y Y Compressor 2 circuit 2 (dependent on unit configuration)
Electrical heaters
enabling
P3
Elec. heater 1 N/Y Y
Only displayed if the electric heaters are present in the unit (option)
Elec. heater 2 N/Y Y
Temperature
setpoint limit
P4
High °C 0 30,0 35,0
Allows to limit the summer and winter setpoints in the setpoint and clock sections, in
addition to the 2°C limitation of the winter setpoint towards the summer one.
Low °C 0 12,0 35,0
Temperature
regulation
P5
Regulation type P/PI P
Choice of the regulation type for the compressors: P (proportional) or PI
(Proportional Integral)
Integration constant s 0 600 1800 Integral constant for PI. Be careful when modifying this parameter.
P6
Summer °C 0 2,0 15,0
Temperature regulation band that corresponds to the proportionnal parameter in the
P or PI summer regulation. See the Compressors control part.
Winter °C 0 2,0 15,0
Temperature regulation band that corresponds to the proportionnal parameter in the
P or PI winter regulation
Dead zone °C 0 0 3,0
Divided by 2, this parameter is the value above or below the setpoint (in summer
or winter mode) to start compressors regulation. See the compressors control part.
Humidity
setpoint limit
P7
High %rH 0 80,0 99.9
Allows to limit the summer and winter humidity setpoints in the setpoint section.
Low %rH 0 20,0 99.9
Dehumidification P8
Enabling N/Y N (option)
Differential %rH 0 5,0 20,0
See the Dehumidification part.
Dead zone %rH 0 0 10,0
Fan speed
management
P9
Decrease if setpoint
reached
N/Y Y If the setpoint is reached, save energy by lowering fan speed