UM AER 01 N 1GB

Table Of Contents
English
46 SysAer
Main
menu Q0
Item
Screen
code
Parameter Unit Min Fact. Max Description / Note
CLOCK
Clock not available J0 This screen appears if the clock board is not connected.
Hour/Date Setting K0
Hour h 0 Hour 23
This screen appears if the clock board is connected.
Minutes min 0 Minutes 59
Day - 1 Day 31
Month - 1 Month 12
Year - 05 Year 99
Week day - The day of the week is automatically deduced from the date.
Password K1 Clock password - 0 - 9999 Enter clock password: 9201
Daily scheduling K2
Enable N/Y N
Daily scheduling enabling. If Yes, the unit operation will be driven by the hour. In all
cases, the unit must be set ON manually (screen N0) to allow the unit starting by
scheduling. If OFF manually, the unit will always stay OFF.
Type
ON/OFF /
Unoccupied
ON/OFF
When enabling the daily scheduling, 2 zones are defined: in and out the band (in
K6). When choosing Unit On/Off, the unit will be OFF outside the band and ON inside
the band. When choosing unoccupied, the unit will remain ON. Inside the band, the
setpoints are those defined in S0/S1 and the unit runs normally. Outside the band,
the setpoints are those defined in K5, and the main fan and the Economizer are
driven in a different way.