UM AER 01 N 1GB
Table Of Contents
- CONTENTS
- 1. INTRODUCTION
- 2. INPUTS/OUTPUTS DESCRIPTION
- 3. ROOM AIR TEMPERATURE CONTROL
- 3.1. SUMMER/WINTER SWITCHING
- 3.2. UNIT ON/OFF
- 3.3. COMPRESSOR CONTROL
- 3.4. DEFROST MODE
- 3.5. MAIN FAN
- 3.6. TEMPERATURE-BASED FREECOOLING AND FREEHEATING CONTROL
- 3.7. THREE DAMPERS ECONOMIZER OPTION
- 3.8. Supply air temperature minimum limit
- 3.9. FRECO OPTION
- 3.10. THERMODYNAMIC RECOVERY OPTION - TRECO
- 3.11. AUXILIARY HEATING
- 3.12. Set point compensation
- 4. ROOM AIR QUALITY CONTROL
- 5. SMOKE DETECTOR
- 6. SCHEDULING
- 7. USER INTERFACE
- 8. ALARM MANAGEMENT
- 9. SERVICING (CAREL)
- 10. MENU DESCRIPTION (CAREL)
English
Information
The access level is automatically reset to the user level after a few minutes.
Access
Services
Commissioning
Status
1/4Main Menu
1/2Main Menu
Access
Status
1/5
18.0°C
20.0°C
16.0bar
5.0bar
Off
Mix air temp.
Return air T.
Condensing P.
Evaporating P.
Compressor
Status
33SysAer
Pressing the "Info" button displays this screen directly.
The authorized menus are displayed according to the access level
selected:
The display has several menus. The "Status" menu is freely accessible.
The other "Installation" and "Maintenance" menus can be displayed and
accessed according to the access level.
To change the access level, go to the "Access" menu and enter the password
corresponding to the level.
The rst line of all the screens integrates the following Information:
² Screen title
² Number of the active line/number of lines of the menu
² Access level
Final user
Installer
Maintenance
To change the access level, go to the "Access" menu and enter the password corresponding to the level.
Final user Installer Maintenance
Password 0534 3260
Status
Installation
Maintenance
Access
7.8.4. MENUS
7.8.4.1. MAIN MENU
7.8.4.2. STATUS MENU
This menu enables the nal user to control the various operating points of
the Treco module of the SysAer.
² compressor
² pressure transducers
² temperature sensors