7.6. ADDRESSES CONFIGURATION
1. To modify the controller address, the terminal must have the address 0.
To modify the terminal address:
² Connect it to a non power supply controller.
² Disconnect the controller from any PLAN connection ( J11 plug).
By default, the controllers are always congured with the PLAN address 1, while the terminals have the
address 32.
The conguration of the addresses of the controllers and the terminals is done with the following procedure:
2. To modify the controller address (with a display whose address is 0):
² Power the controller, pressing the UP, ENTER
and DOWN keys simultaneously; the following
screen will be displayed 2 or 3 seconds later:
² Press the ENTER button to enter the display
address setting eld and press two times the
DOWN key to have the following screen:
² Press ENTER, "Display Address changed" must
appear, then power down the controller
² Power up the controller (with the J11 plug
disconnected).
² After 20 seconds, the following screen must
appear:
As soon as this screen appears, press simultaneously
the UP and ALARM keys, the following screen will be
displayed:
Change the controller PLAN address by pressing the
UP and DOWN buttons, and then press ENTER to
conrm.
Do these 2 procedures for all the controllers of the
PLAN network (address from 1 to 31).