Regulation Manual SysAer SR55 / SR65 / SR80 / SR95 / SR105 / SR120 / SR140 SR160 / SR190 / SR210 Roof-mounted air conditioning unit 49.6 â 210.6kW 49.2 â 216.
CONTROL MANUAL English NOTICE DE REGULATION Français REGELUNGSHANDBUCH Deutsch MANUALE DI REGOLAZIONE Italiano INSTRUCCIONES DE REGULACIÓN Español
English 2 SysAer CONTENTS 1. INTRODUCTION.................................................................................................................................................................................. 3 2. INPUTS/OUTPUTS DESCRIPTION........................................................................................................................................................ 4 2.1. SYSAER SR55 - SR65 - SR80 - SR95 - SR105 - SR120 - SR140...........................................
POWER SUPPLY MUST BE SWITCHED OFF BEFORE STARTING TO WORK IN THE ELECTRIC CONTROL BOX 1.
English 4 SysAer 2. INPUTS/OUTPUTS DESCRIPTION 2.1. SYSAER SR55 - SR65 - SR80 - SR95 - SR105 - SR120 - SR140 2.1.1.
SysAer 5 N° Y1 Y2 Y3 Y4 English 2.1.4. ANALOGUE OUTPUTS Description Economizer damper Heating valve FRECO control Not used 2.2. SYSAER SR160 - SR190 - SR210 2.2.1.
6 SysAer English 2.2.3.
3. ROOM AIR TEMPERATURE CONTROL Room temperature is regulated with following devices: ²²Compressors, ²²Additional heating hot water coil electric coil gas burne ²²Economizer: 2 or 3 dampers ²²Energy recovery system 2 set points can be managed, one for summer mode and one for winter mode. 3.1. SUMMER/WINTER SWITCHING To transition from summer mode to winter mode (and vice versa), proceed as follows: 1.
8 SysAer English 3.2.1. KEYING ON/OFF: Select UNIT ON/OFF from the main menu and press ENTER: pressing the ENTER key on the display, you switch the unit ON and OFF. If the unit is switched OFF via the display, none of the other ON/OFF procedures can be used to switch it back ON. If the unit is OFF, all unit functions and its various controls are disabled, except smoke detection. 3.2.2.
SysAer 9 English 3.3. COMPRESSOR CONTROL The number of compressors and circuits depends on unit configuration. Compressors ON/ OFF is controlled by the room air temperature (RAT). The compressors will not work as long as they are locked in the Service menu (P1 and P2). Operation with 2 Compressors (1/2 circuit) with proportional (P) regulation Dead zone / 2 C1 C2 C1 C2 Room Temp.
10 SysAer English 3.3.2. COMPRESSOR CYCLING The compressor cycling is driven by different delays: ²²Compressor start-up delay after main blower has been started: the compressor will switch ON only when the blower is ON for about 10 seconds. ²²Minimum compressor OFF-time: it makes sure that the compressor stays OFF for a while before it is switched ON again.
3.6.1. SUMMER FREECOOLING The summer freecooling is allowed only if: Outdoor Temp < Room temperature – Freecooling/heating differential, to ensure that outdoor air is cold enough to cool room air. Economizer English SysAer 11 compressor operation Room Temp. 100% 0% FreeC_Diff. The opening of the external damper is controlled by the room air temperature as illustrated in the following figure.
12 SysAer English 3.6.4. NATURAL COOLING COMPRESSOR OPERATION In some cases, the natural cooling conditions are filled but the thermal load of the building does not cool down the building enough. In these conditions, the thermodynamic circuits are used as assistance for natural cooling. In order to protect the thermodynamic circuit, a limited number of compressors can operate: SyAer 55 - 65 - 80 - 95 - 105 - 120 - 140 +1°C 2 1 0 1/2 OAT SyAer 160 - 190 - 210 Economizer +1°C FreeH_Diff.
SysAer 13 The enthalpy-based freecooling and freeheating control feature manages external damper opening based on internal and external enthalpy conditions. With room temperature and air humidity, the controller calculates the room enthalpy (see the Inputs/Outputs menu), with external (outdoor) temperature and humidity, the controller calculates the outdoor enthalpy; and with the temperature and Humidity control set points, it calculates the enthalpy set point.
English 14 SysAer 3.7. THREE DAMPERS ECONOMIZER OPTION The return blower is a part of the 3-Damper economizer option. This fan is controlled in the same way as the main blast fan. If the return blower cuts out, the unit is immediately stopped. 3.8. SUPPLY AIR TEMPERATURE MINIMUM LIMIT The Supply air temperature minimum limit protects the room against sudden drops in temperature and cold air draughts.
SysAer 15 The active recovery is managed by a third party controller but the operating order and operating mode are managed by the main controller.
16 SysAer English 3.10.2. SECONDARY CONTROLLER The TRECO is authorized to start up if the mix air temperature (MAT) is: ²²greater than 5°C in winter ²²less than 40°C in winter If these conditions are not activated ²²TRECO does not start up. ²²An "out of range" message is displayed on the home page. ²²No error message is sent to the main regulator. 3.10.3. OPERATING LIMITS The active recovery controller manages the operating limits of the unit.
SysAer 17 When an auxiliary heating device is present (electrical heaters, hot water coil or gas burner), the management in heating mode related to the compressors can be configured: Via the SERVICE menu, an outdoor air temperature can be set to configure the auxiliary heating element as an extra heater (standard) or to replace the thermodynamic heating.
18 SysAer English 3.11.1. AUXILIARY ELECTRICAL HEATING ELEMENTS This function is only available with the Electrical Heaters (2 stages) option. Auxiliary electrical heating elements are controlled by room air temperature as illustrated in the figure below provided the following conditions are met: ²²The unit is in winter mode ²²Electrical Heaters 1 and 2 are enabled (via the Service menu) EH1 compressor operation EH2 Room Temp. EH_Diff Comp_Diff EH_Offset Winter Setpoint 3.11.2.
SysAer 19 In winter mode, a 0-10V output controls the gas burner capacity according to the figure below: compressor operation Room Temp. 100% 0% Gas_Diff Comp_Diff Gas_Offset Winter Setpoint Maximum Supply Air Temperature limitation If the supplied air is too high, this function can proportionally reduce the burner capacity as the figure below: Normal capacity Room Temp. 0% Gas_Supply_Diff Gas Supply Setpoint The supply setpoint is set to 65°C and the differential to 10°C.
20 SysAer English 3.11.4. GAS BURNER TWO STAGE In Winter mode, two contacts control the gas burner stages as shown in the following diagram: Stage 2 compressor operation Stage 1 Room Temp.
SysAer 21 Set point compensation allows saving energy when external temperature values are particularly unfavourable considering the demands of the room to be controlled. The compensation can also be used to increase the comfort. Compensation varies the control set point according to external temperature. This function is available with the external air temperature sensor. Set point compensation differs between winter mode and summer mode in terms of the type of action and the parameters employed.
22 SysAer English Winter Compensation Winter set point compensation is enabled when the following conditions are encountered: the unit is in winter mode STPCOMP Compensation set point [°C] COMPM Maximum compensation [°C] DIFFC Compensation differential [°C] TEXT External temperature [°C] Compensation - Positive differential Example with manual Heating setpoint = 21°C Heating STP 21°C STPCOMP (10°C) COMPM (2°C) COMPM 19°C TEXT [°C] DIFFC (+10°C) TEXT [°C] DIFFC (0°C) 0°C Compensation - N
5. SMOKE DETECTOR The smoke detector is an option. When smoke is detected in the room air, the exhaust blower and the Economizer (external damper) are managed separately via the Service menu. The unit goes into override shutdown, the main and return fan are stopped but the economizer can be configured open or closed depending on the legislation applicable in the country of installation. 6. SCHEDULING This feature is only available if the board has a clock card fitted.
24 SysAer English 6.2. DAILY SCHEDULING The daily scheduling can be managed by two different ways: ²²ON/OFF ²²Unoccupied mode For both options it is necessary to configure a time band with the Start and End hours, that determines 2 zones: inside and outside the band. 6.3. ON/OFF When the hour is inside the band (between Start and End hours), the unit is switched ON. When the hour is outside the band, the unit is switched OFF.
7. USER INTERFACE The terminal is a 6-button, 4-line x 20-character LCD model, which can display text in various sizes and icons. Alarm Up Prog Enter Escape Down 7.1. KEYPAD ALARM: pressing this key calls up the first active alarm screen. Pressing the key again resets the active alarm or alarms. Various alarm screens can be viewed by pressing UP/DOWN. If no alarms are reported, pressing this key skips to the NO ACTIVE ALARM screen (see Alarm management).
26 SysAer English 7.4. USER INTERFACE CONNECTION The semi-graphic terminal is connected to the controller using the supplied 80cm telephone cable between the back of the terminal and the J10 plug of the controller.
SysAer 27 7.5.1. PRINCIPLE 7.5.1.1. SHAREDE DISPLAY When an installation is composed of many units (in different zones/groups or not), it is possible to connect all the Rooftops together and display each unit parameters using only one interface for the whole installation. 7.5.1.2. MASTER/SLAVE Keeping the unique display, it is also possible to configure the network in Master/Slave.
28 SysAer English Rx-/Tx- Rx+/Tx+ GND Touche de programmation J10 J11 Carte d’horloge FUSIBLE In PLAN, it is possible to connect up to 32 elements (controllers or terminals) identified by their individual address from 1 to 31 for controllers and 1 to 32 for terminals (displays). The 32nd unit must always be a terminal. Be careful: terminals and controllers use the same type of address, so all PLAN elements must have different addresses.
7.6. ADDRESSES CONFIGURATION By default, the controllers are always configured with the PLAN address 1, while the terminals have the address 32. The configuration of the addresses of the controllers and the terminals is done with the following procedure: 1. To modify the controller address, the terminal must have the address 0. To modify the terminal address: ²²Connect it to a non power supply controller. ²²Disconnect the controller from any PLAN connection ( J11 plug).
30 SysAer English Share the terminal for all the controllers: ²²The simplest way to configure a PLAN network is to give to the controllers the addresses from 1 to x and to give to the display(s) the addresses 32, 31, 30 …. ²²Connect the 0-address display to the controller previously chosen (powered or not).
²²In the display address of Trm1, put the address of the display (32 for the example). Press ENTER. In the Pr field of Trm1, put Sh (with the UP and DOWN keys): REMOTE TERMINAL + LOCAL TERMINAL P:11 Adr Priv/Shared Trm1 32 Sh Trm2 None — Trm3 None — Ok?No P:11 Adr Priv/Shared Trm1 32 Sh Trm2 31 Sh Trm3 None — Ok?No ²²Press ENTER five times. In the No field, put Yes and press ENTER. The first screen of the Rooftop software should be displayed now. 7.7.
32 SysAer English 7.8. TRECO FUNCTION CONTROLLER 7.8.1. USER INTERFACE This terminal has a liquid crystal display and has 6 buttons. Up Info Alarm Down Escape Enter 7.8.2. KEYPAD INFO From any screen, this button returns the user to the main menu or home screen and, like the ESCAPE button, invalidates a current modification. ALARM When pressing the alarm button (the red LED flashes if an alarm is active), the alarm management menu is displayed.
SysAer 33 7.8.4.1. MAIN MENU Pressing the "Info" button Main Menu displays this screen directly. The authorized menus are displayed according to the access level selected: Main Menu Status 1/2 Status Access The display has several menus. The "Status" menu is freely accessible. The other "Installation" and "Maintenance" menus can be displayed and accessed according to the access level.
34 SysAer English 7.8.4.3. COMMISSIONING MENU Limited access with the "Installer" or "Maintenance". Main Menu Status 1/4 Commissioning 03.02.2016 Language selection Communications Versions Commissioning 7.8.4.3.1. TIME SETTINGS Services Access Start by configuring the date and time. 1/4 10:40:05 To do so, switch to the "Installer" or "Maintenance" profile in the "Installation" section. The first line of the menu is used to set the date and time. The date and time line will appear as highlighted.
SysAer 35 1/4 Access Service 1/2 Operation hours Operation hours Save / load Compressor 1/3 0.0 h 0 0.0 h -Reversing valve Main Menu Status Save / load SD-Card Settings save-> SD +Settings load <- SD Filter Restart required ! Sett. service load Sett. factory load Sett. service save a-snapshot sa.-> SD BSP load 1/4 1/10 Readwrite Exe Commissioning 7.9.1.
English 36 SysAer 8. ALARM MANAGEMENT 8.1. MAIN CONTROLLER ALARMS (CAREL) When an Alarm is triggered, action is taken on devices, where this option is provided for, and the LED, remote relay and relevant screens are all activated at the same time. To view the alarm triggered, simply press the Alarm key - you can then use the UP/DOWN keys to scroll through the list and view other alarms that might have been triggered.
Code Alarm description Action Reset Delay Notes AL26 B7 sensor fail - OAT - CST 1 / Circuit 1 OFF Manual 60 s Stops the functions Needed for EEV1 AL27 B8 sensor fail - OAT - CST 2 / Circuit 2 OFF Manual 60 s Stops the functions Needed for EEV2 AL28 Electrical Heater thermal lockout Heater 1 OFF Manual No View only AL30 Smoke detector General OFF, parametrable actions on Economizer and Automatic extractor fan No AL31 Circuit 1 High pressure cutout Circuit 1 OFF Automatic No A
38 SysAer English 8.2. ALARM LOG The log is always available. If the board has a clock card fitted, the hour and date of appearance of each alarm are also stored. Logging date and hour Alarm index N°002 12:14 28/11/16 Fan and compressor 1 overload T: 29.5°C U: 37.2%rH Short alarm description Ambient temperature and ambient humidity probes reading logging All the alarms are logged.
SysAer 39 Trigger all circuit breakers. Silence the alarm. Main overview 1/3 requested mode Off from Main Ctrl If at least one alarm or warning is in progress, the alarm button flashes. Operating mode Off to access the latest current alarm. The Press the 'Alarm' button screen displays the latest alarm activated with a description, the date and time at which it occurred. Alarm list detail 1/3 + Therm. flt. cpr1: Active 1 Critical(A) 18.02.
English 40 SysAer Alarm Activation condition Deactivation condition Carel alarm Siemens displayed alarm Mix air temp.: openLoop Mix air T°: openLoop MAT sensor disconnected MAT sensor reconnected x x Mix air temp.: shortedLoop Mix air T°: shortedLoop MAT sensor shorted MAT sensor replaced x x Return air T.: openLoop Return air T°: openLoop RAT sensor disconnected RAT sensor reconnected x x Return air T.
9. SERVICING (CAREL) 9.1. COMPRESSOR AND UNIT HOUR-METER CONTROL At any time, it is possible to check the number of compressors running hours for unit maintenance. When the hour-meter of the individual device reaches the set alarm threshold (Maintenance menu), the maintenance alarm related to the relevant device is activated. The maintenance alarm is a warning-only alarm. 9.2. INPUTS/OUTPUTS TEST All the inputs and outputs can be checked in the Inputs/Outputs menu.
MAINTENANCE Main menu Q0 - Unit Compressor 1 A4 A5 A6 N/Y Compressor 2B Unit Compressor 1 A9 Aa Temperature sensors calibration Ae Defrost period Ai Ah Ag Af Ad Ac Ab N/Y Compressor 2 A8 °C °C S2 Suction sensors °C S1 °C Supply °C °C Room Outdoor min Defrost time Circuit 1/2 N/Y Compressor 2B N/Y N/Y Compressor 2 Alarm history reset N/Y Compressor 1B h h Compressor 1B A7 h h h h h Compressor 2 Maintenance Password h h Compressor 1 Compressor 1B h -
MAINTENANCE Main menu Q0 EEV test Digital outputs test Analogue inputs after treatment Real analogue inputs Humidity / Air quality sensors calibration Pressure sensors Item bar %rH % Pressure sensors Room Humidity Air Quality Aj2 Av Au2 Au1 At As Ar OFF/ON OFF/ON OFF/ON OFF/ON Elec. heater 1 Elec. heater 2 Heat recovery pump General alarm EEV2 manual opening % O N N/Y EEV2 manual N OFF OFF OFF OFF OFF SUM SUM OFF OFF OFF OFF OFF 0 0 0 0 0 Fact. O -99.9 -99.
INPUTS / OUTPUTS HISTORY MAINTENANCE Main menu Q0 Az New password Condensers / defrost sensors I5 Superheat / Air quality I4 I3 I2 EEV circuit 1 and 2 dedicated sensors (available only with RTC units) Humidity sensors I1 Temperature sensors See Alarm log part Ay Ax Analogue outputs Gas outlets Aw % % Economizer opening Hot water valve - New maintenance pwd °C °C Circuit 2 K Superheat 1 Circuit 1 %rH Outdoor % %rH Room Air quality °C CST2 K bar Superheat 2 % EP2 bar
INPUTS / OUTPUTS Main menu Q0 Modem status Analogue outputs Digital outputs Digital inputs Enthalpy Item Ih Ig Ie Id Ic Ib Ia OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON Compressor 2B Electrical Heater 1 Electrical Heater 2 Reversing valve 1 Reversing valve 2 Circuit2 Circuit 1 (option) (option) Digital outputs status Digital inputs status Calculated from the temperature and humidity setpoints If the outdoor temperature and humidity sensors are connected If the room humidity sensor is connect
CLOCK Main menu Q0 K1 K2 Password Daily scheduling Type ON/OFF / Unoccupied N/Y - Week day Enable - Year - - Month Clock password - Day K0 min Minutes Hour/Date Setting h J0 Clock not available Unit Hour Screen Parameter code Item 0 05 1 1 0 0 Min 23 Max ON/OFF N - Year Month Day 9999 99 12 31 Minutes 59 Hour Fact. When enabling the daily scheduling, 2 zones are defined: in and out the band (in K6).
CLOCK Main menu Q0 Ka New password N/Y New Clock pwd - Main fan operation unit OFF by scheduling OFF/ON Week day h : min End K8 h : min Start N/Y °C °C Winter setpoint Summer setpoint Economizer minimum Closed / Set opening position (Pi) Enable K9 Always ON / ON on demand Unit Summer compressors N/Y start K7 K6 K5 K4 K3 Main fan Screen Parameter code Scheduling Weekly scheduling Daily scheduling Unoccupied mode Item 0 0:00 0:00 - OFF N N 0:00 0:00 9999 23:59 2
SETPOINT Main menu Q0 Humidity setpoint Temperature setpoint Item Summer Winter S3 Winter S1 S2 °C Summer S0 %rH %rH °C Unit Screen Parameter code STP high Winter setpoint always used except when the unoccupied mode is limit active and the hour is outside the band. Otherwise, see screen K5. Winter STP high limit winter = Summer STP + 2 Summer setpoint for humidity. Available only if room humidity sensor is connected.
SERVICE Main menu Q0 P7 P8 P9 Dehumidification Fan speed management P6 Humidity setpoint limit Temperature regulation P4 Temperature setpoint limit P5 P3 P2 Electrical heaters enabling Compressors enabling P1 s °C Integration constant Summer N/Y %rH Dead zone Decrease if setpoint reached %rH Differential N/Y P/PI Regulation type Enabling °C Low %rH °C High Low N/Y Elec. heater 2 %rH N/Y Elec.
SERVICE Main menu Q0 Pd Pe Pf Pg Ph FreeCooling / FreeHeating in temp. Summer FreeCooling in temp. Winter FreeHeating in temp. FreeCooling / FreeHeating in enthalpy Atmospheric pressure hPa kJ/kg °C Differential Differential °C °C Differential °C Offset Offset °C N/Y Winter FreeCooling enabling Differential N/Y Winter FreeHeating enabling 800 0 -9.9 -9.9 -9.9 -9.9 0 N/Y Summer FreeCooling enabling 1013 5,0 2,0 2,0 2,0 -2,0 4,0 Y Y Y Temp.
SERVICE Main menu Q0 Setpoint compensation Heat recovery Supply air temperature limitation Economizer/3 dampers Item Pn Pm Pl Pk Pj Pi Analog In. B2 / Manual Unit N/Y °C % N/Y °C Enabling Differential winter Minimum damper opening Summer enabling Differential summer N/Y °C Differential Enabling °C N/Y Enabling Setpoint Closed/Open 0 0 0 0 N 10,0 N 20 6,0 Y 2,0 8,0 Y Closed Normal Normal / Closed Winter start Smoke detection 0-5V 20 Manual Fact.
SERVICE Main menu Q0 Po Pp Pq Pr Ps Pt Pu Pv Pw Winter compensation Automatic changeover Summer room temp. threshold Winter room temp. threshold Room high/low temp. Electrical heaters Hot water coil valve Gas burner Unit °C Max. compensation °C °C Differential N/Y Enabling Offset °C Differential N/Y Enabling °C °C Differential Offset °C °C Low Offset °C High min °C Low Alarm delay °C High N/Y Enable °C °C Max.
SERVICE Main menu Q0 PA PB PC PD PE PF Defrost Clock presence Remote controls Digital inputs Miscellaneous Supervision Py3 Py2 Py1 Px °C Unit N Y ON after blackout Show langage screen N/Y at start-up Random start time ON/OFF by supervisor N/Y N/Y Y N/Y N/Y Summer/Winter ID3 N N N N/Y ON/OFF ID5 10 40 Y 0 0 Y Clock board presence N/Y min min Start delay Maximum duration N/Y Clogged filter switch 100 0 defrosting opening % ON de-frosting on/off 10 % FRECO min.
SERVICE Main menu Q0 PG PK PL PLAN network PJ PI PH Bacnet / DirectConn. / Modbus / Lon / Ana. Modem / GSM Modem / Prog. Load N/Y Disp.
L0 Unit selection UNIT SELECTION N0 Unit status Summer/winter mode R0 N0 PV New password Unit status PU PT PS Smoke detector Thermostat digital inputs configuration unit PP, PQ, PR Each configuration PLAN units configuration Summer/winter change ON/OFF change Unit status New Service pwd -SUMMER-WINTER- Switch ON / OFF - N ID2/ID12/B6 Electrical heaters Activation ID2/ID12/B5 N/Y Summer/Winter Enabling D/S N/Y PM, PO PLAN units activation PN, Each unit activation Unit Scr
M3 M2 M1 M0 Main screens code Starting… : appears for 5 seconds at unit start-up. Mode Unoccupied : if a clock board is present and the Unoccupied option is selected for scheduling, the unit is in unoccupied mode if the hour is outside the programmed hour band. OFF by display : OFF selected via the display ON/OFF OFF by Digital Input : unit OFF by digital input ID5 (if selected in the Service menu) OFF by scheduling : if a clock board is fitted, scheduling can stop the unit.
- - Units connected in Plan Unit Plan configuration M6 / M7 M8 / Electrical heaters / / Air quality Gas burner / / / / Freecooling Temp. Enthalpy Free. / Defrost Freeheating Temp. Unit Item Heat valve M5 M4 Main screens code Address and configuration of the unit connected by Plan, with a Plan address between 2 and 31 English Only on the Plan Master unit. Displays all the units connected by Plan to the Master unit. If one unit is disconnected, its figure is empty.
English 58 SysAer