Abreviaons:
T1: Heat pump leaving water temperature
T1S: Heat pump leaving water set temperature
DISINFECT sets whether or not the DHW pump operates during the DHW tank disinfecon operaon.
PUMP RUNNING TIME sets the length of me the pump runs for at each of the user-specied start mes on the DHW PUMP
tab on the DOMESTIC HOT WATER (DHW) menu, if TIMER RUNNING is enabled.
7.5 COOL MODE SETTING Menu
MENU > FOR SERVICEMAN > COOL MODE SETTING
In COOL MODE SETTING the following parameters should be set.
COOL MODE enables or disables cooling mode. For installaons
with space cooling terminals, select YES to enable cooling mode.
For installaons without space cooling terminals, select NON to
disable cooling mode.
Figure 3-7.15: COOL MODE SETTING menu
T1S RANGE selects the heat pump leaving water set temperature range that is available to the user for cooling mode on the
user interface main screen. LOW or HIGH should be selected to suit the type of space cooling terminals installed. When LOW
is selected, the minimum set temperature is 5°C. If the climate-related curve funcon is selected, the curve selected is the
low temperature curve. When HIGH is selected, the minimum set temperature is 18°C. If the climate-related curve funcon is
selected, the curve selected is the high temperature curve. Climate-related curves refer to Mini Heat Pump Monobloc Series
Engineering Data Book, Part 3, 8.1 “Environment Temperature Curves”.
T4CMAX sets the ambient temperature above which the heat pump will not operate in
cooling mode. For M.HP05/07/09 DCI MONO, the highest value that T4CMAX can take
is 43°C. For M.HP12/14/16 DCI MONO, the highest value that T4CMAX can take is 46°C.
T4CMAX is the cooling mode upper ambient temperature operang limit of the heat
pump. Refer to Figure 3-7.16.
dT1SC sets the minimum temperature dierence between the heat pump leaving
water temperature (T1) and the heat pump leaving water set temperature (T1S) at
which the heat pump provides chilled water to the space cooling terminals. When T1
– T1S ≥ dT1SC the heat pump provides chilled water to the space cooling terminals
and when T1 ≤ T1S the heat pump does not pro water to the space cooling terminals.
dTSC sets the temperature dierence between the actual room temperature (Ta)
Figure 3-7.16: T4CMAX, T4CMIN
Abreviaons:
T4: Outdoor ambient temperature
T4CMIN sets the ambient temperature below which the heat pump will not operate in cooling mode. The lowest value that
T4CMIN can take is -5°C, which is the cooling mode lower ambient temperature operang limit of the heat pump. Refer to
Figure 3-7.16.
and set room temperature (TS) above which the heat pump provides chilled water
to the space cooling terminals. When Ta – TS ≥ dTSC the heat pump provides chilled
water to the space cooling terminals and when Ta ≤ TS the heat pump does not
provide chilled water to the space cooling terminals. Refer to Figure 3-7.18. dTSC is
only applicable if YES is selected for ROOM TEMP in the TEMP. TYPE SETTING menu.
Refer to Part 3, 7.8 “TEMP. TYPE SETTING Menu”.
Figure 3-7.18: dTSC
Figure 3-7.17: dT1SC
COOL
COOL
COOL