SYSTEMP Engineering Data Manual (EDM SYSTEMP S 7GB)
|
 SysTemp R
18
R series close control air conditioners are built and sized in such a 
way that they can be installed alongside data center racks In air con-
ditioning systems for large data centers, the adoption of the follow-
ing design concepts has in fact become an established custom:
  The racks containing servers are increasingly positioned according 
to the Hot Aisle and Cold Aisle layout.
  Air temperatures are allowed to rise up to 30-35°C in the hot aisle 
and 20-25°C in the cold one, with very low humidity (never above 
30%).
  Server performance is increasingly on the rise, while server sizes 
are increasingly reduced. As a result, many more servers can be 
installed in a rack, so some of these racks can be eliminated as 
they are empty. At the same time, heat dissipation increases, 
thereby requiring more power from air conditioners. R series air 
conditioners are designed and built so as to fit into this plant lay-
out perfectly. As a matter of fact:
  They exploit the space left free from racks and allow cold air to be 
distributed as close as possible to servers, that is, where heat is 
generated.
  They feature rear intake from the hot aisle and front supply to 
the cold aisle with a horizontal flow. The horizontal flow reduces 
internal pressure drop, with a consequent reduction in the power 
draw of the fan.
Technical feature
 Very high EER (Energy Efciency Ratio)
  Limited footprint
  Dark gray RAL 7024 metal structure
  Panels with thermo-acoustic insulation
  Front and rear accessibility for easy maintenance
  Cooling, electric and water top/bottom connections
  Electrical panel complete with control and safety devices
  SySmart control microprocessor with LCD graphic display
  G2/G4-class efciency air lters with dirty lter alert (according to 
the size)
  Return air temperature sensor
  Supply air temperature sensor
  Electronic EC fans
  Brushless DC compressors with R410A inverter regulation
  Electronic expansion valves with SysDrive system
  Three-way control valves
  Unit shutdown system for the presence of re
 RS485 and RJ45 ports for Modbus
®
 RTU and TCP/IP
SysTemp R 










