11.10 AIR-COOLED CONDENSER POWER SUPPLY AND REGULATION CONNECTION (ACCESSORY)
Air-cooled condensers can be supplied with two types of electric power supply and regulation, as an accessory:
1) A 230 Vac power supply with cut-o regulation, dedicated to condensers with AC fans.
2) A 230 Vac or 400 Vac protected line (depending on the type of condenser) and a 0-10 Vdc signal line for the regulation of
condensers with EC fans.
When installing the unit, the power supply line of the air-cooled condensers must be set-up as shown in the gure below.
Connection with 230 Vac cut-o regula-
tion
Connection with 0-10 Vdc regulation
and 230 Vac power supply
Connection with 0-10 Vdc regulation
and 400 Vac power supply
The type of cable to be used for the connection must have the following features:
Main features of the connection cable
230 Vac power supply with cut-o regulator
Type FS18OR18 300/500 Vac cable
Shielding Not required
Cross-section and number of conductors
8 A variator 3 x 1.5 mm
2
12 A variator 3 x 2.5 mm
2
Maximum length m 100
Example
230 Vac power supply
Type
FS18OR18 300/500 Vac (1.5-2.5 mm
2
)/ FG16OR16 600/1000 Vac (4 mm
2
) cable)
Shielding Not required
Cross-section and number of conductors
10 A 3 x 1.5 mm
2
16 A 3 x 2.5 mm
2
20 A 3 x 4 mm
2
Maximum length m 100
Example
400 Vac power supply
Type
FS18OR18 300/500 Vac (1.5-2.5 mm
2
)/ FG16OR16 600/1000 Vac (4 mm
2
) cable)
Shielding Not required
Cross-section and number of conductors
10 A 4 x 1.5 mm
2
16 A 4 x 2.5 mm
2
20 A 4 x 4 mm
2
Maximum length m 100
Example
0-10 Vdc regulation signal line
Type FR2OH2R16 450/750 Vac signal transmission cable
Shielding Tinned copper braid - Cover at least 65%
Cross-section and number of conductors 2 x 0.35 mm
2
Maximum length m 100
Example