11.9 CONNECTION OF FREE COOLING PLENUM MOTORISED DAMPER ACTUATORS (ACCESSORY)
The Free Cooling plenum accessory has two motorised dampers controlled by the regulator through a 0-10 Vdc signal.
The damper actuators are supplied mounted on the dampers, and equipped with 3 metres of pre-wired cable in the actua-
tors. The actuator cables have to be connected inside the unit’s electrical panel, as shown in the gure:
Motorised damper actuator
Position of damper actuator connection terminals
Connection of the damper actuators
The type of cable to be used for the connection must have the following features:
Main features of the connection cable
Type FS18OR18 300/500 Vac signal transmission cable
Shielding Not required
Cross-section and number of conductors 3 x 0.5 mm
2
Maximum length m 100
Example