SYSTEMP – Installation Operation Manual (IOM SYSTEMP rev.N)

Table Of Contents
82
11.5 WALL-MOUNTED TEMPERATURE AND HUMIDITY PROBE CONNECTION (ACCESSORY)
The supplied temperature and humidity probe allows managing the room temperature and humidity detection in systems
where return detection is not real or satisfying like, for example, systems with partial outside air introduction in the return.
The supplied probe is of wall installation type. It is recommended to position the probe at a minimum height of 1600 mm
o the oor for the most reliable temperature readings.
The connections must be made as indicated in the electrical wiring diagram supplied with the unit. The gure below shows
the probes connection terminal board and the position of the jumpers for correct operation of said probe.
Wall-mounted temperature and humidity probe
Size and drilling jig for wall-mounted installation
A Probe support
B Connection terminals
C Electronic board
Temperature and humidity probe connection
The type of cable to be used for the connection must have the following features:
Main features of the connection cable
Type FR2OH2R16 450/750 Vac signal transmission cable
Shielding Tinned copper braid - Cover at least 65%
Cross-section and number of conductors 4 x 0.35 mm
2
Maximum length m 100
Example
A
B
C