11.2 ETHERNET RJ45 PORT CONNECTION (Modbus TCP - BACnet IP - Web Server)
The SySmart
3
microprocessors can be connected to a supervision and/or BMS (Building Management System) system,
which adopts the Modbus TCP (Standard) or BACnet IP (Accessory) protocol through a dedicated RJ45 serial board.
Through the RJ45 serial board it is also possible to view supervision Web pages through the Web Server function (Accesso-
ry).
To make the connection to the Ethernet network, simply connect the SySmart
3
microprocessors through the RJ45 port on
the board:
RJ45 Connection (BACnet IP conguration)
A RJ45 Ethernet
The type of cable to be used for the connection must have the following features:
Main features of ethernet communication cable
Type LAN/ethernet cables Cat. 6/6A
Application IEEE 802.3: 10Base-T; 100Base-T; 1000Base-T; 10GBase-T
Shielding Pair shielded with Aluminium/Polyester foil (PiMF)
Cross-section and number of conductors 4 x 2 x 0.13 mm
2
- AWG 26
Stranding Twisted pairs
Maximum DC resistance for conductor at 20°C Ω/km 130
Insulation resistance at 20°C MΩ*km > 2000
Mutual capacitance c-c / c-s pF/km 43
Impedance Ohm 100 +/- 5
Maximum length m 100
Example
A
A