SYSTEMP – Installation Operation Manual (IOM SYSTEMP rev.N)

Table Of Contents
73
10.10 TWO SOURCES COOLING CIRCUIT WITH DOUBLE COMPRESSOR AND REMOTE CONDENSER
The following image represents the cooling circuit in two sources units with double compressor and remote condenser.
Cooling circuit:
Liquid line (HP liq: PS 45 Bar - TS 68 °C):
A Liquid line
B Liquid line cock
C Pressure intake SAE 5/16” male are
D Liquid temperature probe
E Liquid receiver
F Safety valve (44 Bar)
G Dehydrator lter with liquid sight glass
H Electronic expansion valve
Suction line (LP: PS 22 Bar - TS 38 °C):
I Pressure intake SAE 5/16” male are (for
refrigerant charging)
J Direct expansion coil
K Fan
L Evaporation pressure probe
M Suction temperature probe
N Antifreeze hot gas injection valve
Hot gas line (HP gas: PS 41 Bar - TS 64 °C):
O Compressor
P Discharge temperature probe
Q High pressure switch with manual reset
(41 Bar)
R Hot gas line check valve
S Pressure intake SAE 5/16” male are
T Condensation pressure probe
U Hot gas line cock
V Hot gas line
* DC inverter compressor (accessory):
1 DC inverter compressor
2 Oil separator
Water circuit:
a Water inlet
b Inlet water temperature
c Manual air vent valves
d Chilled water coil
e 3-way ball valve
f Water outlet
** 2-way ball valve (accessory)