SYSTEMP – Installation Operation Manual (IOM SYSTEMP rev.N)

Table Of Contents
67
10.4 COOLING CIRCUIT WITH SINGLE COMPRESSOR AND WATER-COOLED CONDENSER
The following image represents the cooling circuit in units with single compressor and air-cooled condenser.
Cooling circuit:
Liquid line (HP: PS 41 Bar - TS 64 °C):
A Water-cooled condenser
B Pressure intake SAE 5/16” male are
C Liquid temperature probe
D Liquid receiver
E Dehydrator lter with liquid sight glass
F Electronic expansion valve
Suction line (LP: PS 22 Bar - TS 38 °C):
G Pressure intake SAE 5/16” male are (for
refrigerant charging)
H Direct expansion coil
I Fan
J Evaporation pressure probe
K Suction temperature probe
Hot gas line (HP: PS 41 Bar - TS 64 °C):
L Compressor
M Discharge temperature probe
N High pressure switch with manual reset (41
Bar)
O Condensation pressure probe
P Pressure intake SAE 5/16” male are
* DC inverter compressor (accessory)
Water circuit:
a Water inlet
b Inlet water temperature for dry cooler regula-
tion (accessory)
c Manual air vent valves
d Adjustment valve of water-cooled condenser
(accessory)
e Water outlet
D
P
E
G
C
B
I
H
J
F
G
O
K
A
N
L
M
a
c
c
d
e
b