SYSTEMP – Installation Operation Manual (IOM SYSTEMP rev.N)

Table Of Contents
66
10.3 COOLING CIRCUIT WITH SINGLE COMPRESSOR AND REMOTE CONDENSER
The following image represents the cooling circuit in units with single compressor and remote condenser.
Liquid line (HP liq: PS 45 Bar - TS 68 °C):
A Liquid line
B Liquid line cock
C Pressure intake SAE 5/16” male are
D Liquid temperature probe
E Liquid receiver
F Safety valve (44 Bar)
G Dehydrator lter with liquid sight glass
H Electronic expansion valve
Suction line (LP: PS 22 Bar - TS 38 °C):
I Pressure intake SAE 5/16” male are (for
refrigerant charging)
J Direct expansion coil
K Fan
L Evaporation pressure probe
M Suction temperature probe
Hot gas line (HP gas: PS 41 Bar - TS 64 °C):
N Compressor
O Discharge temperature probe
P High pressure switch with manual reset
(41 Bar)
Q Hot gas line check valve
R Pressure intake SAE 5/16” male are
S Condensation pressure probe
T Hot gas line cock
U Hot gas line
* DC inverter compressor (accessory):
1 DC inverter compressor
2 Oil separator
** Hot gas post-heating (accessory):
a 3-way hot gas valve
b Check valve
c Hot gas post-heating coil
Q
F
A
R
I
G
D
K
J
L
B
H
I
M
E
C
P
N
O
S
T
U
1
2
a
b
c