SYSTEMP – Installation Operation Manual (IOM SYSTEMP rev.N)
Table Of Contents
- WARRANTY CONDITIONS
- 1 DESCRIPTION OF UNITS AND OPERATING LIMITS
- 2 TRANSPORTATION, POSITIONING AND INSTALLATION PROCEDURES
- 3 PLENUMS, VENTILATED PLENUMS AND DUCT SECTIONS (ACCESSORY)
- 4 FREE COOLING PLENUM (ACCESSORY)
- 5 ADJUSTABLE AND VENTILATED PLINTHS (ACCESSORY)
- 6 TMC AIR-COOLED CONDENSER PLACEMENT AND INSTALLATION
- 7 CONNECTION OF CONDENSATE DISCHARGE AND HUMIDIFIER
- 8 WATER CIRCUIT CONNECTIONS
- 9 COOLING CONNECTIONS
- 9.1 ROUTING OF THE COOLING CIRCUIT PIPES
- 9.2 COOLING CIRCUIT SIZING
- 9.3 COOLING CIRCUIT INSTALLATION
- 9.4 UNIT COOLING PIPE CONNECTION
- 9.5 AIR-COOLED CONDENSER CONNECTION
- 9.6 COOLING CIRCUIT VACUUM DRYING OPERATIONS
- 9.7 CHARGING THE COOLING CIRCUIT
- 9.8 PRECAUTIONS
- 9.9 LUBRICATING OIL FILLING IN THE CIRCUIT
- 9.10 TMC CONDENSER PRESSURE REGULATOR (ACCESSORY)
- 9.11 CHECKING THE REFRIGERANT LOAD AND COOLING CIRCUIT OPERATION
- 9.12 PRECAUTIONS AGAINST REFRIGERANT LEAKS
- 9.13 CHECKING THE MAXIMUM CONCENTRATION OF REFRIGERANT
- 10 EXAMPLES OF WATER AND COOLING CIRCUITS
- 10.1 EXAMPLE OF CHILLED WATER CIRCUIT
- 10.2 TMC AIR-COOLED CONDENSER COOLING CIRCUIT
- 10.3 COOLING CIRCUIT WITH SINGLE COMPRESSOR AND REMOTE CONDENSER
- 10.4 COOLING CIRCUIT WITH SINGLE COMPRESSOR AND WATER-COOLED CONDENSER
- 10.5 COOLING CIRCUIT WITH DOUBLE COMPRESSOR AND REMOTE CONDENSER
- 10.6 COOLING CIRCUIT WITH DOUBLE COMPRESSOR AND WATER-COOLED CONDENSER
- 10.7 TWO SOURCES WATER CIRCUIT WITH CHILLED WATER CIRCUITS
- 10.8 TWO SOURCES COOLING CIRCUIT WITH SINGLE COMPRESSOR AND REMOTE CONDENSER
- 10.9 TWO SOURCES COOLING CIRCUIT WITH SINGLE COMPRESSOR AND WATER-COOLED CONDENSER
- 10.10 TWO SOURCES COOLING CIRCUIT WITH DOUBLE COMPRESSOR AND REMOTE CONDENSER
- 10.11 TWO SOURCES COOLING CIRCUIT WITH DOUBLE COMPRESSOR AND WATER-COOLED CONDENSER
- 10.12 COOLING CIRCUIT WITH FREE COOLING AND SINGLE COMPRESSOR
- 10.13 COOLING CIRCUIT WITH FREE COOLING AND DOUBLE COMPRESSOR
- 11 ELECTRICAL CONNECTIONS
- 11.1 RS485 SERIAL COMMUNICATION BOARD CONNECTION (Modbus RTU - BACnet MS/TP)
- 11.2 ETHERNET RJ45 PORT CONNECTION (Modbus TCP - BACnet IP - Web Server)
- 11.3 CANbus LAN CONNECTION (ACCESSORY)
- 11.4 REMOTE CONTROL TERMINAL CONNECTION (ACCESSORY)
- 11.5 WALL-MOUNTED TEMPERATURE AND HUMIDITY PROBE CONNECTION (ACCESSORY)
- 11.6 DUCTED TEMPERATURE AND HUMIDITY PROBE CONNECTION (ACCESSORY)
- 11.7 CONNECTION OF THE SMOKE AND FLAME DETECTORS SUPPLIED (ACCESSORY)
- 11.8 WATER DETECTION PROBE CONNECTION (ACCESSORY)
- 11.9 CONNECTION OF FREE COOLING PLENUM MOTORISED DAMPER ACTUATORS (ACCESSORY)
- 11.10 AIR-COOLED CONDENSER POWER SUPPLY AND REGULATION CONNECTION (ACCESSORY)
- 12 ROUTINE AND SPECIAL MAINTENANCE
- 13 DEACTIVATION, DISMANTLING AND DISPOSAL
- 14 APPENDIX 1: RECOMMENDED EQUIPMENT
- 15 APPENDIX 2: PRELIMINARY CHECKS AND FIRST START-UP
- 16 APPENDIX 3: FAULT DIAGNOSIS
- 17 NOTES
58
Unit refrigerant content
Standard
models
Unit
Oil separa-
tor
Water-cooled
condenser
Hot gas
Standard
models
Unit
Oil separa-
tor
Water-cooled
condenser
Hot gas
kg kg
P Series
071 2.00 0.15 0.25 0.30 322 2.50 0.20 0.40 0.65
141 2.40 0.20 0.25 0.30 422 2.70 0.20 0.40 -
211 2.60 0.20 0.40 0.45 512 4.40 0.20 0.55 -
251 4.15 0.20 0.55 0.45 662 5.20 0.20 0.70 -
301 5.00 0.20 0.70 0.65 852 5.20 0.20 1.45 -
321 5.00 0.20 0.70 0.65 932 7.70 0.20 1.45 -
361 5.15 0.20 0.90 -
461 5.15 0.20 1.45 -
Free Cooling and Two Sources P Series
211 2.80 0.20 0.40 - 302 2.25 0.20 0.40 -
301 4.10 0.20 0.70 -
512 3.20 0.20 0.55 -
662 4.40 0.20 0.70 -
461 5.80 0.20 1.45 - 852 4.40 0.20 0.90 -
G Series
461 7.60 0.20 1.10 -
612 4.70 0.20 0.55 -
932 7.40 0.20 1.10 -
1342 10,70 - - -
R Series
121 2.10 0.15 - - 231 3.35 0.20 0.40 -
201 2.80 0.20 - - 361 6.00 0.20 0.70 -
Free Cooling and Two Sources R Series
231 3.20 0.20 0.40 -
For models with several circuits the gures are intended per circuit
TMC condenser refrigerant content
Standard models
Condenser LAC valve
Standard models
Condenser LAC valve
kg kg
11 0.45 0.30 49 2.05 1.40
19 0.55 0.40 55 2.05 1.40
31 1.10 0.75 63 2.65 1.75
35 1.55 1.00 84 3.05 2.00
40 1.55 1.00 92 4.10 2.70
Non-TMC condenser refrigerant content
For non TMC condensers, the refrigerant content, expressed in kg, is provided by the following expression:
Coil volume (dm
3
) x Kref = Refrigerant content (kg)
Standard condensers Condensers with LAC valve
Kref Kref
0.37 0.61