8.5 CONNECTION OF THE INTERNAL SUBMERGED ELECTRODE HUMIDIFIER (ACCESSORY)
The units may be tted with a submerged electrode humidier to control environmental humidication.
This type of humidier exploits the conductivity of the water in the cylinder to produce steam. Applying voltage to the
electrodes in the cylinder, current will ow between the electrodes that will heat the water until it reaches boiling point.
The humidier is adjusted with the electronic board installed in the electric panel. The humidier's work conditions may be
checked with the display on the machine.
Submerged electrode humidier
8.5.1 WATER CONNECTIONS OF THE SUBMERGED ELECTRODE HUMIDIFIER
During installation of the unit, you are required to connect the supply piping of the internal humidier to the water line of
the system. The following table shows the type of water connection tting.
Water connections
Flexible hose adaptor Threaded tting
Connection diameter Ø (mm) Connection diameter Ø Threading
External Internal Inches DN ISO 7/1
8 6 3/4 20 Male
Submerged electrode humidier cylinder specications
Values
Humidier model
3 kg/h 8 kg/h 15 kg/h
Steam production kg/h 0.6 - 3.2 1.0 - 8.0 2.0 - 15.0
Cylinder volume dm
3
1.1 - 3.3 0.9 - 5.4 2.2 - 9.8
Instantaneous supply ow rate l/min 0.6 0.6 1.2
Instantaneous discharge ow rate l/min 10