7 CONNECTION OF CONDENSATE DISCHARGE AND HUMIDIFIER
7.1 CONNECTION OF CONDENSATE DISCHARGE AND HUMIDIFIER
RISK OF BURNS!
The drainage water of the humidier may reach temperatures of 100 °C!
All air conditioners, whether direct expansion or water chilled coils, require a condensate discharge connection, and the
humidier discharge of the building waste drainage system.
The trap, essential for draining condensate as the bowl is located in a point of negative pressure, is supplied already installed
on the unit and should be connected when the unit is placed in position by the installer. The discharge pipe is Retiex type with ex-
ternal diameter of 25 mm (internal 19 mm).
The humidier discharge, which does not require a trap, is supplied ready connected to the termination of the condensate
discharge.
Connection of condensate discharge and humidier discharge
Condensate discharge Condensate discharge with humidier
Hose
Connection diameter Ø (mm)
External Internal
25 19
WARNING!
The condensate discharge is supplied with a trap!
Do not remove the trap supplied with the unit!
In order to avoid drainage problems do not add siphons to
the drainage line and plan on a funnel type tting!