6 TMC AIR-COOLED CONDENSER PLACEMENT AND INSTALLATION
6.1 DIMENSIONS FOR INSTALLATION AND CLEARANCES
The gure below shows the dimensions to be taken into account during installation of the TMC air-cooled condensers. For
the exact values referring to the dimensions indicated in the gure, refer to the following table and, in any case, to the drawings
supplied with the order conrmation.
The units must be positioned dierently based on the type of unit, and always following the design and manufacturing
requirements of the unit.
During installation the required spaces for optimal operation must be complied with, as set out in the following table for
standard models (identied by the code number sequence).
TMC condenser dimensions
Vertical Installation (V) Horizontal Installation (H)
Standard models
Length (A)
Depth (B) Height (C)
Fixing holes Ø Weight
V H V H
mm mm mm mm kg
11 882
480 550 510 818 10
27
19 1582 44
31
1225
570 900 830 1050 13
67
35 71
40
2225
104
49 112
55 112
63 120
84
3225
157
92 170
Clearance space calculation
Vertical Installation (V) Horizontal Installation (H)