2 TRANSPORTATION, POSITIONING AND INSTALLATION PROCEDURES
2.1 OVERALL WEIGHT AND CLEARANCES FOR ROUTINE MAINTENANCE
2.1.1 OVERALL WEIGHT
WARNING!
If the units are installed on a normal oor, without vibration damping supports, it is nec-
essary to place a layer of vibration damping material (rubber or equivalent material with
a minimum thickness of 10 mm) between the machine and the oor to avoid transmitting
vibrations to the structure of the building.
This layer of vibration damping material also makes up for oors that are not perfectly at,
guaranteeing the air seal between the elements and containing the noise level of the instal-
lation.
For correct installation of the units, and to ensure safety of the operators, it is essential to make sure that the surface on
which the air conditioners are to be installed is capable of supporting the overall weight.
The overall weight can be found in the table below, for standard models (identied by the code number sequence).
Overall weight
Standard models
Weight +/-5%
Standard models
Weight +/-5%
Standard models
Weight +/-5%
kg kg kg
P Series
071 170 322 430 10 125
141 225 422 535 20 150
211 280 512 540 30 245
251 305 662 685 50 250
301 360 852 705 60 270
321 385 932 745 70 280
361 460 80 375
461 470 110 410
160 690
220 810
Free Cooling and Two Sources P Series
211 310 512 590 50 260
321 420
662 750 70 300
852 770 110 435
461 520 932 1320 160 760
G Series
461 620 70 540 230 XH 1250
612 690 150 840 300 1630
932 910 150 XH 865
1342 1240 230 1220
R Series
121 220 235 235 20 145
201 235 361 235 40 210
Free Cooling and Two Sources R Series
231 270 40 260