SYSTEMP – Installation Operation Manual (IOM SYSTEMP rev.N)

Table Of Contents
118
PRESENCE OF ELECTRIC
ARCS IN CYLINDER
CYLINDER CLOGGED
WITH LIMESCALE
WATER CONDUCTIVITY
HIGH
PRESENCE OF SALT
SOFTENERS
CLEAN CYLINDER AND
REPLACE IF NECESSARY
INSTALL CYLINDER
WITH HIGH
CONDUCTIVITY
REMOVE SOFTENERS
CYLINDER BURNT OUT
WATER SOFTENED OR
DEMINERALISED
WATER CONDUCTIVITY
LOW
DISCHARGE SOLENOID
VALVE BLOCKED
PRESENCE OF SIPHONS
ON STEAM PIPE
REPLACE CYLINDER
USE UNTREATED
POTABLE WATER
INSTALL CYLINDER WITH
LOW CONDUCTIVITY
CHECK VALVE AND
REPLACE IF NECESSARY
REMOVE SIPHONS
CHECK ELECTRONIC
CONTROL BOARD
CHECK ELECTRONIC
CONTROL BOARD
REMOVE SIPHONS
CYLINDER TOO FULL
NO ELECTRICAL POWER
SUPPLY
NO CONTROL SIGNAL
PRESENCE OF SIPHONS
ON DISCHARGE PIPE