16.5 PROBLEMS WITH HUMIDIFICATION
WATER CHARGING
FAILED
NO WATER
CHARGE SOLENOID
VALVE BLOCKED
NO ELECTRICAL POWER
SUPPLY
NO CONTROL SIGNAL
CHECK WATER CIRCUIT
CHECK VALVE AND
REPLACE IF NECESSARY
CHECK ELECTRICAL
POWER SUPPLY CIRCUIT
CHECK ELECTRONIC
CONTROL BOARD
NO WATER
NO CONTROL SIGNAL
CYLINDER BURNT OUT
WATER CONDUCTIVITY
LOW
CHECK WATER CIRCUIT
CHECK ELECTRONIC
CONTROL BOARD
REPLACE CYLINDER
INSTALL CYLINDER WITH
LOW CONDUCTIVITY
CHECK VALVE AND
REPLACE IF NECESSARY
CHECK ELECTRICAL
POWER SUPPLY CIRCUIT
USE UNTREATED
POTABLE WATER
WATER BOILING FAILED
DISCHARGE SOLENOID
VALVE OPEN
NO ELECTRICAL POWER
SUPPLY
WATER SOFTENED OR
DEMINERALISED