SYSTEMP Engineering Data Manual (EDM SYSTEMP S 7GB)

Unit identication and specications
|
33
General
The air conditioners have been specically designed and
manufactured for close control air conditioning where the
handling almost exclusively sensible heat loads is a funda-
mental requirement.
The typical applications are computer rooms, digital tele-
phone exchanges, switch rooms, weather stations, medical
laboratories, CAT and MR scanners, as well as any other
application where a sensible heat load must be dissipated
without modifying the relative humidity.
The series, which can be either upow or downow, offers
a large range of accessories and variations in design, allow-
ing for maximum exibility in the use of the units.
Cabinet and frame structure
The structure is made by aluminum proles painted in
anthracite colour RAL 7024. Panels are made by hot-gal-
vanized sheet steel 1mm-thickness, painted in anthracite
colour RAL 7024 too.
The insulation is high density, A1 class re-resistance poly-
urethane sheets as per norm UNI/ISO 3795, self-extin-
guishing, protected by a plastic lm out friction. The doors
are fastened to the structure with hinges and safety access
keys.
Valid for models:
ST OPA/UPA 361-422-461-512-662-852-932
ST OPU/UPU 60-70-80-110-160-220
ST UGA 932-1342
ST UGU 70-150-230-300.
Unit identication
SysTemp
Air supply type
H Horizontal supply
O Upow air supply
U Downow air supply
Series name
P Close Control air conditioners: pe-
rimeter installation
G Air conditioners for large data
centres: perimeter installation
R Air conditioners for large data
centres: in row installation
Nominal size
(nominal cooling capacity in kW)
ST O P A 07 1 a TS
Cooling type
A Direct expansion coil
U Chilled water coil
Series modication index
Accessories
TS Two Sources
FC Free Cooling
Number of cooling circuits
(Only direct expansion units)
Unit identifcation and specications