SYSTEMP Engineering Data Manual (EDM SYSTEMP S 7GB)
Unit identication and specications
|
33
General
The air conditioners have been specically designed and
manufactured for close control air conditioning where the
handling almost exclusively sensible heat loads is a funda-
mental requirement.
The typical applications are computer rooms, digital tele-
phone exchanges, switch rooms, weather stations, medical
laboratories, CAT and MR scanners, as well as any other
application where a sensible heat load must be dissipated
without modifying the relative humidity.
The series, which can be either upow or downow, offers
a large range of accessories and variations in design, allow-
ing for maximum exibility in the use of the units.
Cabinet and frame structure
The structure is made by aluminum proles painted in
anthracite colour RAL 7024. Panels are made by hot-gal-
vanized sheet steel 1mm-thickness, painted in anthracite
colour RAL 7024 too.
The insulation is high density, A1 class re-resistance poly-
urethane sheets as per norm UNI/ISO 3795, self-extin-
guishing, protected by a plastic lm out friction. The doors
are fastened to the structure with hinges and safety access
keys.
Valid for models:
ST OPA/UPA 361-422-461-512-662-852-932
ST OPU/UPU 60-70-80-110-160-220
ST UGA 932-1342
ST UGU 70-150-230-300.
Unit identication
SysTemp
Air supply type
H Horizontal supply
O Upow air supply
U Downow air supply
Series name
P Close Control air conditioners: pe-
rimeter installation
G Air conditioners for large data
centres: perimeter installation
R Air conditioners for large data
centres: in row installation
Nominal size
(nominal cooling capacity in kW)
ST O P A 07 1 a TS
Cooling type
A Direct expansion coil
U Chilled water coil
Series modication index
Accessories
TS Two Sources
FC Free Cooling
Number of cooling circuits
(Only direct expansion units)
Unit identifcation and specications