SYSTEMP Engineering Data Manual (EDM SYSTEMP S 7GB)

|
Technical data
28
Cooling circuit with single compressor and remote condenser
The following image represents the cooling circuit in units with single compressor and remote condenser.
Liquid line (HP liq: PS 45 Bar - TS 68 °C):
A Liquid line
B Liquid line cock
C Pressure intake SAE 5/16” male are
D Liquid temperature probe
E Liquid receiver
F Safety valve (44 Bar)
G Dehydrator lter with liquid sight glass
H Electronic expansion valve
Suction line (LP: PS 22 Bar - TS 38 °C):
I Pressure intake SAE 5/16” male are (for
refrigerant charging)
J Direct expansion coil
K Fan
L Evaporation pressure probe
M Suction temperature probe
Hot gas line (HP gas: PS 41 Bar - TS 64 °C):
N Compressor
O Discharge temperature probe
P High pressure switch with manual reset
(41 Bar)
Q Hot gas line check valve
R Pressure intake SAE 5/16” male are
S Condensation pressure probe
T Hot gas line cock
U Hot gas line
* DC inverter compressor (accessory):
1 DC inverter compressor
2 Oil separator
F
A
R
I
G
D
K
J
L
B
H
I
Q
M
E
C
P
N
O
S
T
U
1