Water condenser connection (accessory)
Water connections
Standard
models
Plate condenser Adjustment valve
Water circuit volume
Fitting diameter Ø Threading Fitting diameter Ø Threading
Inches DN ISO 7/1 Inches DN ISO 7/1 dm3
P Series
071 - 141
3/4” 20
Male
1” 25
Female
0.7
211 1.5
251
1-1/4” 32
1.6
321
1-1/4” 32
2
361 2.5
461 3
322 - 422
3/4” 20
1” 25 1.2
512
1-1/4” 32
1.6
662
1-1/4” 32
2
852 2.5
932 3
G Series
612 3/4 20
Male 1-1/4” 32 Female
1.6
461 - 932 1-1/4” 32 3
R Series
231 3/4 20
Male
1” 25
Female
1.2
361 1-1/4” 32 1-1/4” 32 2
For models with several circuits the gures are intended per circuit
Free Cooling unit water circuits connection (accessory)
Water connections
Standard models
Fitting diameter Ø Threading Water circuit volume
Inches DN ISO 7/1 dm
3
P Series
321
1-1/4” 32
Female
18
461 - 512
1-1/2” 40
26.5
662 – 852 33.5
R Series
231 1” 25 Female 17.5
Chilled water coil connection-two sources design (accesory)
Water connections
Standard models
Fitting diameter Ø Threading Water circuit volume
Inches DN ISO 7/1 dm
3
P Series
50 3/4” 20
Female
5
211 1” 25 5.5
321
1-1/4” 32
18
70 16
110 22
461 - 512
1-1/2” 40
22.5
662 – 852 27.5
932 34,8
160 28.5
R Series
231 1” 25
Female
15.5
40 1-1/4” 32 22.5