| | | | | | | | | | | | | ☞ www.ziehlabegg.com CZ D DK E F FIN GB I NL P PL RU S english Fcontrol FXDM Frequency inverter with integrated sine lter for 3 ~ fans Quick Start Guide Detailed Description on www.ziehl-abegg.com Software version: D1333A from Version 2.37 L-BAL-E223-GB 1623 Index 003 Part.-No.
Quick Start Guide Fcontrol – model series FXDM Content 1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Structure of the short operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 3 2 Safety instructions . . . . . . . . . . . . . . . . . . . . .
Quick Start Guide Fcontrol – model series FXDM 1 1.1 General notes General notes Structure of the short operating instructions Attention! This Quick Start Guide contains basic information on safety, use, installation and quick commissioning. The detailed Operating Instructions can be found on our website. The additional information they contain must be observed. To download the Operating Instructions, go to www.ziehl-abegg.com and enter the article number “Part No.
Quick Start Guide Fcontrol – model series FXDM 2.3 Product overview Work on the device Information Mounting, electrical connection, and start-up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)! Danger due to electric current • It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP00! It is possible to touch hazardous voltages directly.
Quick Start Guide Fcontrol – model series FXDM 3.3 Mounting Maintenance The device must be checked for soiling and, if necessary, cleaned in periodic intervals. The ventilation grilles on the bottom and on the top of the device must be free to ensure adequate cooling of the device. They can be cleaned with a vacuum cleaner, broom or brush. 3.4 Transport • • • • 3.5 Storage • • • 3.6 The device is packed ex factory to suit the transport method previously agreed.
Quick Start Guide Fcontrol – model series FXDM 4.2 Mounting Minimum space requirement In order to ensure sufficient ventilation of the device, clearance on all sides of at least 50 mm has to be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance applies to the installation of several devices next to each other. When installing several devices on top of each other, the danger of reciprocal heating exists.
Quick Start Guide Fcontrol – model series FXDM Mounting Type FXDM5...18 (FXDM22) Fastening at 4 points 1 2 4 3 GM00005A_M 15.12.2015 " Drill fastening points “1” - “4”. " Fasten device with screws. Type FXDM32...50 (IP54 / IP65) Fastening at 8 points 1 2 5 6 8 7 GM00002A_M 15.12.2015 4 3 " Drill 8 fastening points. " Screw in fastening point screws “1” - “4” up to a distance of approx. 5 mm and mount the device.
Quick Start Guide Fcontrol – model series FXDM Mounting Type FXDM32...50 (IP20) Fastening at 4 points 2 1 GM00001A_M 15.12.2015 4 3 " Drill 4 fastening points. " Screw in screws “1” - “4” up to a distance of approx. 5 mm and mount the device. " Tighten fastening point screws “1” - “4”. 4.4 Cable inlet " Remove the terminal compartment cover. " Depending on the housing model cut off necessary cable inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands.
Quick Start Guide Fcontrol – model series FXDM Electrical installation Sheet metal housing IP54 IP20 1 2 3 1 2 3 4 Inlet mains connection (40 mm) Inlet motor connection (40 mm) Inlet control cables (20 mm) Inlet mains connection (32 mm) Inlet motor connection (32 mm) Ridges for connecting the control cables Cut-out for control cables in the cover Information • Cable glands can be used alternatively (not included in delivery).
Quick Start Guide Fcontrol – model series FXDM Electrical installation Example: Position of terminals for devices in sheet metal housing 1 2 3 4 5 Line Motor Modulation Indication relays MODBUS Terminal Information Mains connection Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specifications (see Technical data and nameplate affixed to the side).
Quick Start Guide Fcontrol – model series FXDM Electrical installation Terminal Information 24V - GND 24V DC Out Voltage supply For external devices, e.g. for sensors, terminal. E1 - GND, E2 - GND Analog In 1 / 2 Analog inputs For speed setting signal or sensor signal. Connection depending on programmed function, see selection Mode. GND, A (D+), B (D-) RS-485 MODBUS Interface for networking via MODBUS RTU.
Quick Start Guide Fcontrol – model series FXDM 6 6.1 Base setup Base setup Jumper for the input signal Jumper position factory setting for 0 - 10 V signal. For temperature sensors (TF..) or sensors with 4 - 20 mA bring the internal jumper for the external signal in the correct position. Caution- not under voltage! Observe the savety notices! When using “other sensors” bring the jumper in the correct position. The adjustment of the measuring range takes place in the Base setup of respective Mode.
Quick Start Guide Fcontrol – model series FXDM 6.2 Base setup Select operation mode Information Simple installation is possible through the selection of the preprogrammed mode of operation. This determines the basic function of the device; factory setting 1.01 = Speed controller (activation via 0 - 10 V signal). The controller configuration is automatically carried out during selection of the application related mode of operation.
Quick Start Guide Fcontrol – model series FXDM 7 7.1 Start-up Start-up Prerequisites for commissioning Attention! 1. You must mount and connect the device in accordance with the operating instructions. 2. Double check that all connections are correct. 3. The mains voltage must match the information on the rating plate. 4. The rated current on the rating plate will not be exceeded. 5. Make sure that no persons or objects are in the hazardous area. 7.
Quick Start Guide Fcontrol – model series FXDM Start-up Switch Motor to ON in menu group “Start” 1 2 3 P 7.3 5 4 6 P ▲ Menu Mode 1.01 Start Info Setting Events Base setup Controller Setup OFF Motor 0.0 Hz Frequency 50.0 Hz Set Internal1 -0Motor fault 1.01 Mode OFF |1A | PIN ProtecA Function tion ---PIN input 0.0 A Motor current ----Set Internal2 -1Overtemperature 0 - 10 V OFF E1 Analog Set protecIn tion -2ext.
Quick Start Guide Fcontrol – model series FXDM 8 8.1 Controls and Menu Controls and Menu Multipurpose LC display and keyboard 2 3 4 5 6 7 8 9 10 1 11 12 19.02.2014 v_display_erklaerung_fcontrol.vsd 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.
Quick Start Guide Fcontrol – model series FXDM Controls and Menu In the menu point “Language” display language can be selected. One returns to the menu group “Start” using the ESC (▼ + ▲) shortcut keys. 8.
Quick Start Guide Fcontrol – model series FXDM 9 9.1 Enclosure Enclosure Technical data Rated current* Output {1} [A] Rated current (I fundamental component @ 50 Hz) Input {2} [A] Rated temperature 2.5 FXDM5AM (308138) Max. heat dissipation approx. {2} [W] Noise approx. {4} [dB] Weight [kg] [°C] max. line fuse {3} [A] Housing protection IP 2.5 (2.3) 40 6 50 - 3.3 54 5 4.8 (4.4) 50 10 100 54.6 7.2 54 FXDM5M (308137) 5 4.8 (4.4) 50 10 100 54.6 7.
Quick Start Guide Fcontrol – model series FXDM Rated current* Output {1} [A] Rated current (I fundamental component @ 50 Hz) Input {2} [A] Rated temperature FXDM40ME (308175) 40 FXDM50AM (308183) Enclosure Max. heat dissipation approx. {2} [W] Noise approx. {4} [dB] Weight [kg] [°C] max. line fuse {3} [A] Housing protection IP 34.0 (31.5) 50 50 790 65.7 33.1 20 50 47.5 (43.2) 50 63 910 65.7 32.8 54 FXDM50AM (308227) 50 47.5 (43.2) 50 63 910 65.7 32.
Quick Start Guide Fcontrol – model series FXDM Enclosure For devices > 16A and ≤ 75A according to EN61000-3-12 (see Electrical Installation / Harmonics current and line impedance) Please ask manufacturer for the individual harmonic oscillation levels of the current as a percentage of the fundamental oscillation of the rated current. FXDM2.5(A)M...22(A)M and FXDM32(A)ME...
Quick Start Guide Fcontrol – model series FXDM 9.2 Enclosure Connection diagram Fcontrol FXDM...(A)M V 8 mA Kontaktbelastung Contact rating max. AC 250 V 2 A E1 14 12 K1 L1 L2 L3 21 24 Digital In 1 GND TB/ TB/ D1 TP TP 22 Analog Out 1 D1 24 V DC Out Analog In 1 Analog In 2 Digital In 2 A GND 24V 24V E1 GND E2 GND D2 D2 Normal A B 24V GND (D+) (D-) K2 N U V W Eingang Input 0...10 V(PWM) 0...20 mA 4...20 mA TF..(KTY) ≥ 10 mm² / 2x Ausgang Output 0...
Quick Start Guide Fcontrol – model series FXDM 9.3 Enclosure Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: ZIEHL-ABEGG SE Heinz-Ziehl-Straße 74653 Künzelsau Telephone: +49 (0) 7940 16-0 Telefax: +49 (0) 7940 16-504 info@ziehl-abegg.de http://www.ziehl-abegg.de 9.