MANUAL AW AR EBM003 MIN

Electrical connection |
7
8 Electrical connection
Safety information
Observe 2 Important safety information, page 1
Prevent the ingress of water into the connection box.
Connection
Check if the data on the nameplate matches the
connection data.
Complete the electrical connection according to the
circuit diagram.
Fans with EC- motors must be switched on/off via the
control input.
Connect the cable end in a dry environment.
Install a circuit breaker in the permanent electrical
installation, with a contact opening of at least 3 mm
at each pole.
Protective grounding wire
The protective grounding must have a cross-section equal to or greater than that of the phase conductor.
Residual current circuit breaker
All-current-sensitive residual current circuit breakers are required for use in alternating-current systems with 50/60
Hz, in combination with electronic devices such as EC motors, frequency converters or uninterruptible power supplies
(UPS).
Table 3 Description of electrical connections of the following fans: AW 200 EC sileo (#35854), AW 250 EC sileo
(#35855), AW 300 EC sileo (#35857), AW 350 EC sileo (#35859)AW 400 EC sileo (#35860), AW 450 EC sileo
(#35863)
Wire
no.
Connection Color
Function/assignment
CON10 L
black or
brown
Power supply, see name plate for voltage range
CON11 N
blue Neutral conductor
CON12 PE
green/
yellow
Protective conductor
1 GND
blue GND-connection of the controller interface
2 0...10 V PWM
yellow Controller input 0...10 V or PWM
3 10 V
red
Voltage output 10 V / Short-circuit-proof power supply for external
devices (e.g. poti)
I max=1.1mA:
AW 200 EC sileo (#35854)AW 250 EC sileo (#35855), AW 300 EC sileo
(#35857), AW 450 EC sileo (#35863)
I max=10mA:
AW 350 EC sileo (#35859)AW 400 EC sileo (#35860)
4
Tacho*
white
Speed output: Open Collector, 1 impulse per revolution, electrically
isolated, Isink_max = 10 mA
NC*
white 1
Status relais, open for failure
COM*
white 2
* Not available with every device