MA FRICO SIRE COMPETENT FUNCTIONS AC GB 160830

SIRe Competent Air Curtains
9
Time between
opening [s]
High speed
over run [s]
Low speed
over run [s]
t < 60
30 90
60 < t < 300
10 300
t > 300
0 180
Heating settings
Week program
Fan settings
>Installer menu
>Installer menu>Fan settings>Door
over run
Over run mode
Auto
>Installer menu>Fan settings>Door
over run
Over run mode
High speed over run
Low speed over run
Door mode
Fan speed increase
Door over run
>Installer menu>Fan settings
>Installer menu>Fan settings>Door
over run
Over run mode
Fixed time
>Installer menu>Fan settings>Door
over run
Over run mode
High speed over run
Low speed over run
>Installer menu>Fan settings
Door over run
Door mode
>Installer menu>Fan settings
Door mode
Fixed flexible
GB
Fan settings
Make settings for fan mode (see also
Operating modes section).
Door over run
Settings for overrun.
Door mode
There are three different door modes to
choose from; Auto, Fixed flexible and Fixed
open.
In Fixed flexible mode, the control function
notes whether the door is open or closed.
In Fixed open mode the door is considered
always open and is only controlled according
to Current stage. In Auto mode, the control
automatically switches between Fixed flexible
and Fixed open modes depending on how
often the door has been open.
In over run mode Auto, SIRe controls the over
run time depending on how frequently the
door is opened between openings, according
to fixed preset values, according to the table.
Over run mode Fixed time is selected is one
wants fixed over run times, the times can be
changed during High speed over run and Low
speed over run.
Factory setting
Over run mode: Auto (Set time)
High speed over run: 30 s (0 – 180 s)
Low speed over run: 120 s (0 – 300 s)
Factory setting
Door mode: Fixed flexible (Fixed open/Auto)