Function description of current stage
The task of the Current stage function is to
balance the room climate when a door is
always open by using the right combination of
fan and heating step.
In open mode, the room temperature is
read every 60 seconds (during the first 6
cycles, and then every 5 minutes and at each
reading any Current stage adjustments are
made, i.e. fan control and supplied output
adjusted.
Winter
When winter mode is selected under Main
Menu > Summer / Winter.
If the room temperature is more than 3
degrees below the current settings, the
current stage increases by 2 steps.
If the room temperature is between 1 and
3 degrees below the current settings, the
current stage increases by 1 step.
If the room temperature is more than 2
degrees above the current setting, the
current stage decreases by 1 step.
Summer
When summer mode is selected under Main
Menu > Summer/Winter, heating is blocked.
If the room temperature is more than
2 degrees below the current settings, the
current stage increases by 1 step.
If the room temperature is between 1 and
2 degrees below the current settings, the
current stage decreases by 1 step.
If the room temperature is more than 2
degrees greater than the Current settings,
current stage increases by 1 step.
If the room temperature is between 1 and 2
degrees above current settings, the current
stage decreases by 1 step.
If fan control has been max. limited under
Main Menu > Fan control> High speed limit,
all current stages will be used but the fan will
be limited to the current setting.
See the table on the next page.