MA FRICO SIRE COMPETENT FUNCTIONS AC GB 160830
SIRe Competent Air Curtains
15
37°C 40°C 50°C 54°C
47°C 52°C 57°C 61°C
GB
Unit with electrical heating except
PA2500E
Unit with water heating and PA2500E
Decrease heat Heat off Full speed
Overheat protection - temperature limits
Air curtains
Frost protection function
Unit with water heating
Only applies to units with internal sensor.
The frost protection function is intended to
prevent the water coil from freezing.
If the internal temperature falls below +5 °C
frost protection alarm A3 is given, the valve
actuator opens and the fan stops.
Note! In event of repeated alarms, overheating
alarms and frost protection alarms, carry out
a thorough check and if the fault cause cannot
be found contact authorised installer or Frico.
Start ramp-up
Alarm