MA FRICO SIRE COMPETENT FUNCTIONS AC GB 160830
SIRe Competent Air Curtains
10
Filter guard settings
Fan settings
Heating settings
>Installer menu
>Installer menu>Heating
settings
Open door setp. diff.
• 3.0 K
>Installer menu>Heating
settings
Sensor calibration
Open door setp. diff.
>Installer menu>Heating
settings
Heating step diff.
• 1.0 K
>Installer menu>Heating
settings
Heating step limit
Open door setp. diff.
Heating step diff.
Heating step limit
• 3
Sensor calibration
Heating step diff.
Heating step limit
>Installer menu>Heating
settings
>Installer menu>Heating
settings
Control range limit
>Installer menu>Heating
settings
• 35°C
>Installer menu>Heating
settings
Sensor calibration
Open door setp. diff.
Control range limit
>Installer menu>Heating
settings
Control range limit
Heating step limit
Sensor calibration
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
Outdoor temp. sensor
• 0.0 K
Control range limit
GB
Heating settings
Make settings for heating.
Open door setp. diff.
Set by how much the set point value (Room
temp. day/night) is to increase when the door
is open.
Factory setting
Set point value difference open door: 3.0K (0K
– -10K)
Heating step diff.
Unit with electrical heating
The temperature difference between
connection of the electrical heating step.
Factory setting
Heating step diff: 1.0K (0K – 10K)
Heating step limit
Unit with electrical heating
Possibility of limiting the heating.
Factory setting
Heating step limit: 2/3 (1-2/3)
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for example +2K gives an increase of the
displayed value of 2 degrees).
Factory setting
Room temperature sensor: 0.0K (-10K – 10K)
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35°C.
Factory setting
Control range limit temperature: 35°C (5 –
35°C)