DOP KBR(F)006

Declaration of Performance
3 (4)KBR(F) / F400 (120)/280...355 mm_006
ANNEX 1 / Complementary information on Installation / Application (EN 12101–3:2015 / Table F.8)
Mechanically driven exhaust appliances for smoke and heat control fans
Classification
Class Temperature [°C] Time [min]
[X]
F
200
200 120
[X]
F
300
300 60
[X]
F
400
400 120
[X]
F
400
400 90
[ ]
F
600
600 60
[ ]
F
842
-
1) Location of the fan and insulation if so
[X] outside the building without thermal insulation
[ ] outside the building including thermal insulation
[X] inside the building but outside of the smoke reservoir without thermal insulation
[ ] inside the building but outside of the smoke reservoir including thermal insulation
[ ] inside the smoke reservoir
2) Installation
The specifications in the fan`s manual regarding permissible installation positions of the fan have to be considered.
[X] horizontal motor shaft, floor standing
[X] horizontal motor shaft, wall mounted
[ ] horizontal motor shaft, suspended from ceiling
[ ] vertical motor shaft, impeller below the motor
[ ] vertical motor shaft, impeller above the motor
[ ] vertical motor shaft, mounted onto the face of wall
[ ] vertical motor shaft, suspended from ceiling
Mechanically driven exhaust appliances for smoke and heat control fans
3) Flexible connections tested with the fan
[X] flexible connection inlet side
[X] flexible connection outlet side
[X] flexible connection inlet and outlet side
[ ] flexible connection cooling air connection
4) Cooling air
[ ] c
Air,q
Volumetric flow cooling air Air = min. volumetric flow q = max. cooling air temperature
6) Snow load
[ ] SL0 without deflector
[ ]
SL125
[ ]
SL250
[ ]
SL500
[ ] SL1000 with deflector FSL
[ ]
SLA