SYSHP MINI EVO P – Installation Operation Manual (IOM SYSHP MINI EVO P S 1GB)

39
a) Procedure
Connect the cable to the appropriate terminals as
shown in the picture.
Fix the cable reliably.
Control port signal type
Voltage
Maximum running current(A)
Wiring size(mm
2
)
Type 2
220-240VAC
0.2
0.75
3) For outside pump :
zone2 pump
P_c
KM2
Power supply
7 5 3 1
A1
A2
2468
9
20
CN11
P_c
C1
outside circulation pump P_o
KM3
Power supply
7 5 3 1
A1
A2
2468
10
21
CN11
P_0
C1
DHW pipe pump
P_d
KM5
Power supply
7 5 3 1
A1
A2
2468
12
23
CN11
P_d
C1
outside solar energy pump P_s
KM4
Power supply
7 5 3 1
A1
A2
2468
CN11
11
22
P_s
C1
KM6
Power supply
7 5 3 1
A1
A2
2468
24
23
CN11
P_xC1
4) For
alarm or Defrost run(P_x)
Alarm or Defrost
a) Procedure
Connect the cable to the appropriate terminals as
shown in the picture.
Fix the cable reliably.
Control port signal type
Voltage
Maximum running current(A)
Wiring size(mm
2
)
Type 2
220-240VAC
0.2
0.75